Example configuration
Relay
Relay internal name
Linked function
Select the function for tripping the output relay (for multiple association use “User Variable”)
Operation Logic
Not Used
Logical Status
Relay Logical status
Output Configuration
Normally Deenergized
The output relay is deenergized in normal conditions and gets energized
on activation of the controlling Functional Output; reset means
deenergizing.
Normally Energized
The output relay is energized in normal conditions and gets deenergized
on activation of the controlling Functional Output; reset means
energizing.
tON (Operation Time)
This timer controls the duration of the activation of the output relay.
tON
:
0
(0.01-10)s, step 0.01s
Relay Status
Relay
– Physical status