Functions - Operation Mode
Automatic
:
In this mode the output relay is “operated” (energized if “N.D.”, deenergized if
“N.E.”) when the controlling Functional Output is activated and it is reset to the “non
operated” condition when the Functional Output gets disactivated but, anyhow, not
before the time “tON” has elapsed (minimum duration of the operation time)
Manual
:
In this mode the output relay is “operated” when the controlling Functional Output is
activated and remains in the operated condition until a manual reset command is
issued by the relay keyboard (local commands menu) or via the serial
communication. In this mode the timer “tON” has no effect.
Impulsive
:
In this mode the output relay is “operated” when the controlling Functional Output is
activate
d and it remains in the “operated” condition (energized if “N.D.”,
deenergized if “N.E.”) for the set time “tON” independently from the status of the
controlling Functional Output.
Open “MSCom2” program and connect to the relay.
Selec
t “Change Windows” from “Menu” button
Select “DO Configuration”