2.4 - Configuration of the output relays (see § 5)
The different functions of the relay can be programmed to operate any of the output relays as
explained in § 5.
The functions are more than the available output relays but some of then can be grouped to operate
the same relay according to the protection system.
For generator protection the different functions normally operate the trippings shown in the tabel here
below.
PROTEC.
DEVICE
OPERATED
OUTPUT RELAY
CONTROLLED
FUNCTION
EMERG. MACHINE
FIELD SIGNALS OR
TRIP
C/B
C/B
OTHER
R1
R2
R3
R4
32
= Ir>
X
X
X
X
40
= Zc<
X
X
46-1
= 1Is
X
X
X
46-2
= 2Is
(X)
X
50-1
= I>
(X)
(X)
50-2
= I>>
(X)
(X)
51-1
= tI>
X
X
X
X
51-2
= tI>>
X
X
X
X
50G
= O>
(X)
51G
= tO>
(X)
X
X
(X)
(X)
X
X
(X)
(X) = if required ; X = needed