36
9.0
Appendix A - Specifications and
Features
GENERAL - ALL EXTENDED CIRCUITS ARE SUPERVISED
Note:
The
Minimum Signal Strength
, measured by LQI (Link Quality Indicator which
is the quality of the received signal strength in the presence of ambient noise) for
each WIO and ZC-301W link, must be 60. A 60 LQI or higher is acceptable. This
measurement can be viewed via the LCD menu display at each Zone Controller.
Table 6 Wireless Input/Output unit Specifications
WR-3001R/W Wireless Input/Output unit (WIO)
Operating:
Temperature
Humidity
-20°C to 49°C (-4°F to 120°F)
Max. 93%@ 32°C non-condensing
Electrical ratings
AC line voltage
120 VAC 60 Hz, 193mA /240 VAC 50 Hz, 124mA
SUPERVISED
Wireless
characteristics
Broadcast Frequency
2.4 GHz
Transmit power
19
dBm
Receive sensitivity
-
10
0 dBm
Battery
Type
Manufactured by Mircom
Model BT-026
3.7 nominal voltage, SUPERVISED, 9000mAH
Lithium Ion Pack With Protection Circuit
Transfer to battery voltage when there is no AC
power
Battery Standby Time
24 hours
Minimum 2 hours of operation (based on the
connected notification appliance’s candela
setting)
29 hours and 5 minutes of alarm at 30mA
Charging capability
9 AH batteries
Maximum charging current
1.8 A
Maximum Load on
NAC circuit
200mA at 24VDC REGULATED
Compliance
Applicable Standards
UL864 and ULC S527 Control Units and
Accessories
Environmental
Use in indoor and dry environment only
i