background image

SS-400-002 

1 I56-3313-000R

MIX-5251AP, MIX-5251RAP and MIX-5251HAP

Intelligent Plug-In Temperature Sensors

INSTALLATION AND MAINTENANCE INSTRUCTIONS

25 Interchange Way, Vaughan, Ontario L4K-5W3

905-660-4655, FAX: 905-660-4113

BEFORE INSTALLING

This sensor must be installed in compliance with the control panel system 

installation manual. The installation must meet the requirements of the Au-

thority Having Jurisdiction (AHJ). Sensors offer maximum performance when 

installed in compliance with the National Fire Protection Association (NFPA); 

see NFPA 72.
Please read the system wiring and installation manual thoroughly. This man-

ual provides detailed information on sensor spacing, placement, zoning, and 

special applications. Copies of these manuals are available from Mircom.

GENERAL DESCRIPTION

Models MIX-5251AP, MIX-5251RAP and MIX-5251HAP are intelligent sen-

sors that utilize a state-of-the-art thermistor sensing circuit for fast response. 

These sensors are designed to provide open area protection with 50 foot 

spacing capability as approved by UL 521. Model MIX-5251AP is a fixed tem-

perature sensor with 135°F fixed temperature alarm. Model MIX-5251RAP is 

a rate-of-rise temperature sensor with 135°F fixed temperature alarm. Model 

MIX-5251HAP is a high temperature sensor with 190°F fixed temperature 

alarm.
Two LEDs on each sensor light to provide 360° visibility of the sensor indica-

tion. The LEDs can be latched ON by code command from the panel for an 

alarm indication. The LEDs can also be unlatched to the normal condition 

by code command. Remote LED annunciator capability is available as an 

optional accessory (Part No. RA400Z/RA100Z).

Models MIX-5251AP, MIX-5251RAP and MIX-5251HAP require compat-

ible addressable communications to function properly. Connect these 

sensors to listed-compatible control panels only.
WIRING GUIDE

All wiring must be installed in compliance with the National Electrical Code, 

applicable local codes and the Authority Having Jurisdiction. Proper wire 

gauges should be used. The installation wires should be color coded to limit 

wiring mistakes and ease system troubleshooting. Improper connections will 

prevent a system from responding properly in the event of a fire.

Remove power from the communication line before installing sensors.

1.   Wire the sensor base (supplied separately) per the wiring diagram, see 

Figure 1.

2.   Set the desired address on the sensor address switches, see Figure 2.

3.   Install the sensor into the sensor base. Push the sensor into the base 

while turning it clockwise to secure it in place.

4.   After all sensors have been installed, apply power to the control unit and 

activate the communication line.

5.   Test the sensor(s) as described in the TESTING section of this manual.

TAMPER RESISTANCE

The sensor bases have a tamper-resistant capability. When this capability is 

enabled, sensors cannot be removed from the base without the use of a small 

SPECIFICATIONS

Diameter: 

6.1 inches (155 mm) installed in B210LP; 4.1 inches (104 mm) installed in B501

Height: 

2.0 inches (51 mm)

Weight: 

4.8 ounces (137 gm)

Installation Temperatures: 

–4°F to 100°F (–20°C to 38°C); MIX-5251AP and MIX-5251RAP; –4°F to 150°F (–20°C to 66°C); MIX-5251HAP

Operating Humidity Range: 

10% to 93% Relative Humidity Non-condensing

Mounting: 

B210LP flanged base; B501 flangeless base

Voltage Range: 

15 to 32 Volts DC Peak

Standby Current: 

300 µA @ 24 VDC (one communication every 5 seconds with LED blink enabled)

LED Current: 

6.5 mA @ 24 VDC

Fixed Temperature Rating: 

135°F (57°C); MIX-5251AP and MIX-5251RAP; 190°F (88°C); MIX-5251HAP

Rate of Rise Detection: 

Responds to greater than 15°F/min.; MIX-5251RAP

screwdriver or other similar tool. Refer to the sensor base installation instruc-

tion manual for details in using this capability.

TESTING

Before testing, notify the proper authorities that the system is undergoing 

maintenance, and will temporarily be out of service. Disable the system to 

prevent unwanted alarms. 
All sensors must be tested after installation and periodically thereafter. Test-

ing methods must satisfy the Authority Having Jurisdiction (AHJ). Sensors 

offer maximum performance when tested and maintained in compliance with 

NFPA 72. The sensor may be tested in the following ways:

A. TEST MAGNET (MODEL NO. M02-04)

 

1.    Place the magnet against the cover in the magnet test area as 

shown in Figure 3 to activate the test feature.

 

2.   The LEDs should latch ON within 10 seconds, indicating alarm and 

annunciating the panel.

 

3.  Reset the detector at the system control panel.

B. DIRECT HEAT METHOD (HAIR DRyER OF 1000 – 1500 WATTS)

 

1.   From the side of the detector, direct the heat toward the sensor. Hold 

the heat source about 6 inches (15cm) away to prevent damage to 

the cover during testing.

 

2.   The LEDs on the detector should light when the temperature at the 

detector reaches the alarm set point. If the LEDs fail to light, check 

the power to the detector and the wiring in the detector base.

 

3.  Reset the detector at the system control panel.

Detectors that fail these tests should be cleaned as described under MAIN-

TENANCE and retested. If the detectors still fail these tests they should be 

returned for repair.

MAINTENANCE

NOTE: Before cleaning notify the proper authorities that the system is un-

dergoing maintenance, and therefore the system will temporarily be out of 

service. Disable the loop or system undergoing maintenance to prevent un-

wanted alarms.

It is recommended that the sensor be removed from its mounting base for 

easier cleaning and that sensors be cleaned at least once a year. Use a vac-

uum cleaner to remove dust from the sensing chamber.

firealarmresources.com

Reviews: