19
Service Manual
www.microphase.eu
Dc
Ground bar
Earth point connection
L bar
Bar's section
0,5 .. 1m
30 x 5 mm
1..2m
40 x 5 mm
Motor and Power cable (as norm EN60204)
Control signals cable (as norm EN60204)
Feedback signals cable (as norm EN60204)
Make sure that the servodrive and the motor are connected to earth in accordance with the current
norms. This connection must be done by using a copper bar, mounted on insulating supports:
L bar
then follow these indications:
1. Connect to the ground bar:
the GND pin 4 of the Dc One
the internal "0V" zero voltage of the CNC;
the earth terminals of the PLC/CNC frames;
the "0V" of the auxiliary supply;
2. Connect the ground bar to the zinced panel of the drive by using a screw, then connect that screw
to earth.
3. Connect earth to the motor’s
It suggests a conductive connection as much as possible to the chassis, or the heatsink,
or the mounting panel of the electrical box.
It refers to the earth connection.
3.1
Connections to earth and ground
SECTION
0,5mm
2
/ 20AWG
SECTION
0,25 - 0,35mm
2
/ 22 -24AWG
SECTION
SIZE (A)
1,5mm
2
/ 15AWG
2/4 4/8 7/14
2,5mm
2
/ 13-14AWG
10/20 14/28 20/40
4mm
2
/ 11-12AWG
30/60