Note:
Additional explanation on the zero point adjustment and installation height of the sensor
Assumption: Measurement range of the 4-20mA pressure sensor 0-5m
Installation situation of the pressure sensor
1
Installation height: 15 cm
3
Output value of the sensor: 6 cm
2
Pressure sensor
4
Measured fill level: 20 cm
Parameter
Value
Mode
4-20 mA
0%
0
100%
5
Trim
-0.01
Sensor offset
0.15
Unit
m
Required configuration
Explanation: When comparing the measured fill level with the output value of the sensor taking the installation
height into consideration, it was determined that the value was 1 cm too high. As the "Trim" and "Sensor offset"
parameters are added to the scaled measurement value, this error can be balanced out by setting the "Trim"
parameter value to -0.01 m.
70