"Calibration" tab
1 Lower reference point (target value in mA) 6 Calculated slope
2 Upper reference point (target value in mA) 7 Button for adopting the lower reference
point for universal input 1
3 Raw value
8 Button for adopting the upper reference
point for universal input 1
4 Rescaled raw value in mA (calculated with
the currently valid values for the offset
and slope)
9 Button for adopting the lower reference
point for both universal inputs
5 Calculated offset
10 Button for adopting the upper reference
point for both universal inputs
8. Set your current source to the value that you want to use for the upper reference point and
wait 3-5 seconds until the value displayed by the DeviceConfig has stabilised. Ensure that the
required value is entered for the upper reference point before you press the button to adopt
the upper reference point for the relevant universal input (see ""Calibration" tab " on page
124). You can also use the "Set all upper" button to set the upper reference points for both of
124
Rev. 01