9.2.1.3.3 Alarms
"Digital" mode
WA
A "high" at the universal input triggers a "warning".
AL
A "high" at the universal input triggers an "alarm".
SW
A "high" at the universal input triggers a "fault warning".
SA
A "high" at the universal input triggers a "fault alarm".
All other modes
Warning Value low
A warning is triggered, if the measurement value
drops to or below this value.
Value high
A warning is triggered, if the measurement value
meets or exceeds this value.
Alarm
Value low
An alarm is triggered, if the measurement value
drops to or below this value.
Value high
An alarm is triggered, if the measurement value
meets or exceeds this value.
Hyst %
Hysteresis for the all-clear in the event of an alarm/warning (e.g.
Hyst=5%, alarm or warning at 100 -> all-clear at 95) or reset the
trigger (e.g. Hyst=5%, level = greater or equal, trigger at 100 -> reset
at 95)
9.2.1.3.4 Trigger
QU
The "Record interval on event" should be used.
XM
Initiate transmission
QX
The "Transmission cycle quick" should be used.
Level
Levels for initiating the trigger. The hysteresis from the "Alarm" tab is used to
determine the level to reset the trigger.
Greater or
equal
The measurement value must be greater or equal to the level to
initiate the trigger.
Less or equal
The measurement value must be less or equal to the level to initiate
the trigger.
9.2.1.4 Calculated channels
Note: The values of the calculated channels are directly calculated for every data output (display on the myDatanet
server or download from the myDatanet server). They are not saved in the server database.
9.2.1.4.1 Basis
Title 1-5
Freely selectable channel title for the calculated channels [0-16 characters]