Chapter 7 Installation
Baud rate
600-115200
Stop bits
1, 2
Parity
N, E, O
Data bits
7, 8
Load
resistance
Off
120Ω
The 120Ω load resistance between RS485 A and B can be activated via the "RS485_Init()" function.
Schematic diagram of the switchable load resistance
Note:
Additional explanation regarding the connection of two RS485 bus participants
Schematic diagram: Connection of two RS485 bus participants
A problem occurs if there is no connection between the GND potentials of the sender and recipient. A common
mode voltage (V
CM
) occurs in this case. The GND potential difference must not exceed max. +/- 7V . Higher
voltages will damage the interface. Temporary overvoltages (ESD, EFT and surge) are, however, absorbed by
protective circuits.
Note: The common mode input voltage range of -7V...+12V specified for the RS485 is determined from the
max. permissible GND potential difference (+/- 7V ) and the max. permissible output voltage range of 0...5 V for
RS485.
7.6.6 Technical details about the RS232 interface
Note:
The RS232 interface of the myDatalogEASY V3 is compatible with standard TIA/EIA-232-F.
The output drivers are protected against overloading and are not damaged by a short circuit to the GND or +/-
15 V. The inputs are equipped with a 5 kΩ load resistance.
Rev. 05
67
Summary of Contents for myDatalogEASY V3
Page 2: ......
Page 13: ...Chapter 2 Declaration of conformity Chapter 2 Declaration of conformity Rev 05 13 ...
Page 14: ......
Page 42: ......
Page 76: ......
Page 88: ......
Page 102: ......
Page 110: ......
Page 116: ......
Page 234: ......
Page 244: ......
Page 252: ......
Page 254: ......
Page 266: ......
Page 276: ......