Baud rate
600-115200
Stop bits
1, 2
Parity
N, E, O
Data bits
7, 8
Flow control Off
RTS/CTS
The direction of the signals corresponds to that of a DTE (e.g. PC).
Signal Type
Low
High
TXD
O
-5,4V
5,4V
RXD
I
<0,8V
>2V
CTS
I
<0,8V
>2V
RTS
O
-5,4V
5,4V
Switching thresholds
7.6.7 Technical details about the USB interface
The connection to a PC is established via the USB slave interface. It is only designated for the communication
with the web-based development environment rapidM2M Studio or the DeviceConfig configuration program.
It is not possible to access the USB interface via the device logic. A detailed description of the rapidM2M
Studio web-based development environment is provided in chapter "rapidM2M Studio " on page 111.
Explanations regarding the functionality of the DeviceConfig configuration program is provided in chapter
"DeviceConfig " on page 89.
Access to the web-based development environment rapidM2M Studio is included in the Microtronics Partner
Program, for which you can register free of charge at the following address:
https://partner.microtronics.com
The DeviceConfig configuration program can be downloaded free of charge from the following website:
www.microtronics.com/deviceconfig
Important note:
If the antenna of the device is earthed or connected to the ground potential of
another object (e.g. installation on a control cabinet), remove the antennas before you connect the
device with the USB interface of a PC. Otherwise, this can cause a potential displacement between
the ground of the antenna and the ground of the PC, which could damage the USB interface of the
device.
68
Rev. 05
Summary of Contents for myDatalogEASY V3
Page 2: ......
Page 13: ...Chapter 2 Declaration of conformity Chapter 2 Declaration of conformity Rev 05 13 ...
Page 14: ......
Page 42: ......
Page 76: ......
Page 88: ......
Page 102: ......
Page 110: ......
Page 116: ......
Page 234: ......
Page 244: ......
Page 252: ......
Page 254: ......
Page 266: ......
Page 276: ......