Flashing
code
Description
Solution/cause
0x
Transport lock (GPRS OFF, measurement
OFF)
If the ALOHA transmission mode is
initiated by the button or solenoid switch ,
the myDatalogEASYplus switches back into
"RUN" mode (GPRS ON, measurement
ON).
1x
Last connection OK
---
2x
Last transmission faulty
Try again later
4x
Standby (GPRS ON, measurement OFF)
see "transport lock"
6x
Offline (GPRS OFF, measurement ON)
see "transport lock"
7x
Network block/no matching provider
l
Improve position of the antenna
l
Check whether the device is located
in the coverage area of a service
provider that is supported by the
integrated SIM chip
(www.microtronics.at/footprint)
l
Lift the network block (see
"myDatanetDeviceConfig Manual "
805004)
8x
No GSM network
l
Try again later
l
Improve position of the antenna
10x
No GPRS connection
Improve position of the antenna
11x
No myDatanet server accessible
l
Check whether port 51241 is enabled
on the myDatanet server
l
Try again later
12x
Faulty SIM chip
Contact support
Error/status codes
Status LED
Description
Flickering Establishing connection
Lights up
GPRS connection established or button/solenoid switch actuated
Off
Normal measuring operation according to configuration until the next transmission
Operating states
9.1.1.2 Button
The button can be used to initiate the ALOHA transmission mode or to instruct the device to
immediately issue the error/status code.
64
Rev. 06
Summary of Contents for myDatalogEASYplus
Page 2: ......
Page 8: ...Chapter 18 Contact information 139 8 Rev 06 ...
Page 9: ...Chapter 2 Declaration of conformity Chapter 2 Declaration of conformity Rev 06 9 ...
Page 10: ......
Page 22: ......
Page 40: ......
Page 62: ......
Page 101: ...Chapter 9 User interfaces 9 2 2 4 GPRS SIM tariff Selected SIM tariff Rev 06 101 ...
Page 102: ......
Page 110: ......
Page 112: ......
Page 118: ......
Page 120: ......
Page 136: ......
Page 138: ......