9.2.1.4.3 Alarms
Note: The evaluation of the alarm thresholds for calculated channels can only occur if the device has transferred
the measurement data to the myDatanet server.
Alarm low
An alarm is triggered, if the measurement value drops to or below this value.
Alarm high
An alarm is triggered, if the measurement value meets or exceeds this value.
Hyst %
Hysteresis for the all-clear in the event of an alarm/warning (e.g. Hyst=5%, alarm or
warning at 100 -> all-clear at 95) or reset the trigger (e.g. Hyst=5%, level = greater or
equal, trigger at 100 -> reset at 95)
9.2.1.5 Output channels
9.2.1.5.1 Basis
Ext warmup time
Indicates the amount of time that an output channel is switched on in "Ext warmup time"
mode before the measurement
Title 1
Freely selectable channel title for the switchable sensor supply
Title 2
Freely selectable channel title for the isolated switch contact
88
Rev. 06