10.2.1.1.6 Alarm settings
"Alarm settings" configuration section
1
Selection of how alarms should be acknowledged
Standard
The global server setting is used to determine whether alarms must be acknowledged
automatically or manually (see "myDatanet Server Manual " 805002)
automatic
Alarms are acknowledged automatically as soon as all of the messages have been sent.
If SMS that have a tariff with a delivery confirmation function have also been sent,
acknowledgement is provided after delivery confirmation.
manual
Alarms must be acknowledged by the user.
2
Alarm in case the device does not respond for longer than the set number of transmission cycles. An
additional tolerance of 10 min. is granted per transmission cycle to take any retries when establishing a
connection into consideration.
Example: Transmission cycle: 60 min; 3x transmission cycles -> Alarm after > 03:30
3
Selection of the how the transfer volume alarm should be handled
Standard
The setting for the transfer volume alarm is taken from the global server settings(see
"myDatanet Server Manual " 805002)
Off
The transfer volume alarm is deactivated.
individual
The level at which the transfer volume alarm should be triggered can be entered in the
adjacent field in KiB.
88
Rev. 01
Summary of Contents for myDatalogGauge 3G
Page 2: ......
Page 10: ...2 2 BLE Gauge 10 Rev 01 ...
Page 11: ...Chapter 2 Declaration of conformity Rev 01 11 ...
Page 12: ......
Page 13: ...Chapter 3 Ex certification Chapter 3 Ex certification 3 1 BLE 3G Gateway ATEX Rev 01 13 ...
Page 14: ...14 Rev 01 ...
Page 15: ...Chapter 3 Ex certification Rev 01 15 ...
Page 16: ...16 Rev 01 ...
Page 17: ...Chapter 3 Ex certification 3 2 BLE Gauge Rev 01 17 ...
Page 18: ...18 Rev 01 ...
Page 19: ...Chapter 3 Ex certification Rev 01 19 ...
Page 20: ...20 Rev 01 ...
Page 134: ......
Page 140: ......
Page 152: ......
Page 154: ......