Chapter 10 User interfaces
Note:
Additional explanation: Delta mode
Assumption:
The source channel contains the counter reading of an infinite counter in m
3
. The calculated
channel 1 should contain the flow rate in m
3
/s and calculated channel 2 should contain the flow rate in l/h.
Parameter
Value channel 1 Value channel 2
Basis -> mode
Delta
Delta
Basis -> unit
m
3
/s
l/h
Calculation ->
time basis
Seconds
Hours
Calculation ->
offset
0
0
Calculation ->
factor
1
1000
Required configuration
Source
Calculated channel 1
Calculated channel 2
Date/time
Infinite counter [m
3
]
Flow rate [m
3
/s]
Flow rate [l/h]
26.03.2013 12:50
900
0
1)
0
1)
26.03.2013 12:51
960
1
3,600,000
26.03.2013 12:52
990
0.5
1,800,000
26.03.2013 12:53
1005
0.25
900,000
26.03.2013 12:54
1065
1
3,600,000
1)
Calculation not possible as there is no measurement value before 12:50.
Explanation:
No values can be determined for the measurement at 12:50 for the calculated channels as there
is no previous value and the difference between the counter readings cannot be determined. For the
measurement at 12:51, the difference to the counter reading is 60m
3
and the time difference is 60sec.
Result = { (value difference / time difference [sec.]) * time basis [sec] * factor } + offset
The result for calculated channel 1 (time basis "Seconds", offset "0" and factor "1") is calculated as follows:
Channel 1 = { (60m
3
/ 60sec.) * 1 * 1 } + 0 = 1m
3
/s
The result for calculated channel 2 (time basis "Hours", offset "0" and factor "1000") is calculated as follows:
Channel 2 = { (60m
3
/ 60sec.) * 3600 * 1000 } + 0 = 3,600,000l/h
10.2.1.2.4.3 Alarms
Note:
The evaluation of the alarm thresholds for calculated channels can only occur if the device has
transferred the measurement data to the myDatanet server.
Alarm low
An alarm is triggered, if the measurement value drops to or below this value.
Alarm high
An alarm is triggered, if the measurement value meets or exceeds this value.
Hyst %
Hysteresis for all-clear in event of alarm/warning (e.g. Hyst = 5%, alarm or warning at 100 -
> all-clear at 95)
Rev. 01
97
Summary of Contents for myDatalogGauge 3G
Page 2: ......
Page 10: ...2 2 BLE Gauge 10 Rev 01 ...
Page 11: ...Chapter 2 Declaration of conformity Rev 01 11 ...
Page 12: ......
Page 13: ...Chapter 3 Ex certification Chapter 3 Ex certification 3 1 BLE 3G Gateway ATEX Rev 01 13 ...
Page 14: ...14 Rev 01 ...
Page 15: ...Chapter 3 Ex certification Rev 01 15 ...
Page 16: ...16 Rev 01 ...
Page 17: ...Chapter 3 Ex certification 3 2 BLE Gauge Rev 01 17 ...
Page 18: ...18 Rev 01 ...
Page 19: ...Chapter 3 Ex certification Rev 01 19 ...
Page 20: ...20 Rev 01 ...
Page 134: ......
Page 140: ......
Page 152: ......
Page 154: ......