5.1.2 Overflow module
This module monitors the measurement range limits of the raw value. If a universal input was, for
example, switched to "Freq" mode, a raw value of above 1000Hz leads to a violation of the
measurement range. The overflow module is only available for the 2 universal inputs in "Freq" and
"PWM" channel modes.
The following table specifies the relevant parameters for the module:
Configuration section
Mode
Parameter
Explanation
Measurement channels -
>Config.
Digital
---
---
Cnt.Day
Cnt.Intervl.
Freq
Out of
range
Procedure in the event of measurement
range violations
PWM
5.1.3 Scale module
This module rescales the raw value (e.g. frequency) to the required measurement value (e.g. mm).
The scale module is only available for the 2 universal inputs.
The following table specifies the relevant parameters for the module:
Configuration section
Mode
Parameter
Explanation
Measurement channels ->
Basis
Digital
Invert
Inverts the input signal
Cnt.Day
Pulse
Count value of an impulse in the
measurement unit
Cnt.Intrvl.
Freq
Factor
Factor by which the input signal is
multiplied
PWM
0%
Start of the measurement range in the
measurement unit
100%
End of the measurement range in the
measurement unit
5.1.4 Decay module
The decay module is designed to summarise several measurement values. The average value over a
required time frame or the minimum value within a required time frame can be determined, for
example. The decay module is only available for the 2 universal inputs, with the exception of
"Cnt.Day" channel mode.
28
Rev. 01
Summary of Contents for myDatalogNANO Ex
Page 2: ......
Page 8: ......
Page 9: ...Chapter 2 Declaration of conformity Chapter 2 Declaration of conformity Rev 01 9 ...
Page 10: ...2 1 Declaration of conformity Appendix 10 Rev 01 ...
Page 11: ...Chapter 2 Declaration of conformity Rev 01 11 ...
Page 12: ......
Page 24: ......
Page 52: ......
Page 78: ......
Page 86: ......
Page 92: ......
Page 104: ......
Page 108: ......
Page 110: ......