5.1.1 Filter module
The filter module is designed to compensate for brief fluctuations to the input signal. This module is only
available for the 5 universal inputs.
The following table specifies the relevant parameters for the module:
Configuration section
Mode
Typ
Parameter
Explanation
Measurement channels ->
Config.
Digital
---
Filter time
Time in [ms] during which the signal must
remain constant to initiate a level change.
Used to suppress brief faults
(debouncing).
Cnt.Day
Cnt.Intervl.
Freq
PWM
Voltage
0-2V
Filter time
Time in [ms] during which the analogue
signal is averaged for signal smoothing.
Used to suppress signal noise.
0-20mA
Adapter
4-20mA
Adapter
PT1000
---
Filter time
Time in [ms] during which the analogue
signal is averaged for signal smoothing.
Used to suppress signal noise.
KTY81110
KTY81210
NI1000
TK5000
26
Rev. 02
Summary of Contents for myDatalogNANO