background image

The 24 volt Combination Valve serves four functions: 

1.

Main Manual Gas Shut-off, 

2.

Manifold

gas pressure regulation, 

3.

Automatic electric main gas valve; single seated on Model 400B-02,

double seated (redundant) on Model 400B-02P, and 

4.

Pilotstat safety control. A pilot adjustment

screw and filter are also included.

The pilot adjustment screw is located on the inlet end of the valve body. Remove plug for

access and turn clockwise to reduce flow.

The main gas regulator, which has an outlet pressure setting range of 2.0"  to 4.0" W.C. NAT-

URAL (8.0"  to 11.0" W.C. PROPANE) is factory set for a manifold gas pressure of 2.0" W.C. NAT-
URAL (8.0" W.C. PROPANE). If pressure adjustment is required for setting capacity, remove regu-
lator cap for access to slotted adjustment screw. Turning of adjustment screw counterclockwise
reduces pressure; clockwise increases pressure. Do not adjust past point  where no change in
pressure is noted.

Note:

Pressure setting can only be made with burner running and gas on. Manifold gas pressure

tap is located in spud holder (See Figure 6 or 7).

CAUTION: If gas supply pressure is below its specified range during adjust-

ment, an overfire condition could result when pressure returns to normal, par-
ticularly if the regulator adjustment screw is bottomed out.

ALWAYS confirm that

at least the minimum rated gas pressure is being supplied to the burner during regulator
adjustments, and NEVER bottom out regulator screw.

If the pressure regulator fails to maintain a constant manifold gas pressure within ±0.1" W.C.,

and it is confirmed that the inlet gas pressure to the Combination Valve is a steady 14.0" W.C.
maximum during standby, and a steady 5.0" W.C. minimum with the flame on, the regulator portion
of the valve is defective and the entire valve must be replaced.

The pilotstat safety control may be suspect, if frequent 

pilot outages

occur. Refer to Section

IX, 2 thru 5, for the method of isolating the problem.

If, on a call for heat, the main burner fails to operate even though the pilot is burning and the

motor is running, failure of the electric valve operator(s) may be indicated. Refer to the 

Trouble

Chart

for further information.

10

Consumer Instructions

CAUTION: If the Combination Valve has been moved or replaced, soap bub-

ble test for leaks with the burner running.

If leakage through the valve occurs, as evidenced by an abnormally large yellow (sooty) flame

on standby, the entire valve should be replaced.

Keep the area around the burner clear and free of combustible materials, gasoline and other

flammable liquids or vapors. Do not obstruct burner air inlet slots or ventilation grilles for combus-
tion air.

The motor features permanently lubricated ball bearings and requires no routine oiling mainte-

nance.

IMPORTANT:

Check the burner flame seasonally. A proper NATURAL gas flame will appear blue

at the burner face with orange and yellow tips. A proper PROPANE gas flame will appear blue at
the burner face with yellow tips. If the flame is too rich, it will appear billowy and yellow with hazy
tips. If too lean, it will appear short and all blue. If the flame does not appear proper,

CONTACT A

QUALIFIED SERVICE TECHNICIAN FOR CLEANING AND/OR READJUSTMENT.

WARNING: If any flame is observed other than pilot when the burner is on

standby, or valve operator is heard to come on before the motor reaches oper-
ating speed, immediately turn off the manual gas control and burner power. A
dangerous condition has developed and must be corrected. 

CONTACT A QUALI-

FIED SERVICE TECHNICIAN FOR CLEANING READJUSTMENT AND/OR REPAIR.

WARNING: If PROPANE gas is used and the burner is located in a base-

ment, crawl space or confining space, contact your gas supplier about
installing a GAS LEAK warning device. PROPANE gas is heavier than air and
can settle in low areas or confined spaces. This would create a danger of
explosion or fire. If you suspect a gas leak, follow instructions on front cover
of this manual.

XI Combination

Gas Valve

Maintenance

Summary of Contents for Economite 400B-02 Series

Page 1: ...tion equipment and remove such hazards Affix this manual adjacent to the conversion burner CODE COMPLIANCE IS THE SOLE RESPONSIBILITY OF THE INSTALLER WARNING If the information in these instructions...

Page 2: ...g provision must be made for an outside air supply near the gas utilization equipment area Install permanently open grilles sized at not less than one square inch free area per 4 000 BTU of burner inp...

Page 3: ...NG Burner cabinet must be mounted in orientation shown in figures 1 and 2 Any other mountings may cause a dangerous condition and will void burner warranty and agency approvals Non standard arrangemen...

Page 4: ...rsely affect burner operation or if flue gas spillage might introduce a hazard If such a device is used it shall be of the listed type and installed and adjusted by a qual ified service technician in...

Page 5: ...of 5 0 W C pressure 11 0 W C PROPANE to the inlet of the Combination Valve when the burner and all other gas utilization equipment are on Note If there is more than 1 0 W C differential in the inlet p...

Page 6: ...and install the spud with the correct orifice size stamped with inch diameter from the SPUD KIT bag If the required firing rate is at the minimum of a capacity range select the next lower range spud...

Page 7: ...ustment 8 Turn operating control to ON or set thermostat above room temperature Main flame should come on when the motor reaches operating speed If not refer to Trouble Chart To make a preliminary set...

Page 8: ...C for NATUR AL gas 8 0 W C for PROPANE 1 Standby gas pressure inches W C 2 The efficiency of the thermocouple and the pilotstat safety control can be determined by timing the safety shut off With the...

Page 9: ...te and electrical interlock switch so as to prevent the burner from firing if the Blower Wheel is not running at its operat ing speed When the motor is off the actuator spring forces the disk against...

Page 10: ...u 5 for the method of isolating the problem If on a call for heat the main burner fails to operate even though the pilot is burning and the motor is running failure of the electric valve operator s ma...

Page 11: ...t flame gas pressure See Section IX Venturi Casting and Pilot E Clogged pilot orifice s See Section IX Venturi Casting and Pilot F Defective ignitor ignitor wires spark rod or improper spark gap See F...

Page 12: ...ent closed too far D Dirty Blower Wheel A Electric Valve Operator s of Combination Valve is defective and entire valve must be replaced Normal low voltage Motor running 24V minimum Combination Valve e...

Reviews: