background image

Standard burners are approved
for use with NATURAL or
PROPANE gas only, and should
be used only with the gas spec-
ified on rating plate.

A Standard Model 400B-02

burner is equipped with a single
seated Combination Valve and
is suitable for NATURAL gas
only. A Standard Model 400B-
02P is equipped with a double
seated (redundant)
Combination Valve and is suit-
able for PROPANE gas use.

WARNING: The

Model 400B-02 is not suit-
able for conversion to
PROPANE gas. Using
PROPANE gas in the
Model 400B-02 is a safety
hazard and will void the
approval listing and the
burner warranty.

Model 400B-02 (NATURAL gas burner is shipped with a .343 diameter orifice installed for an

input capacity range of approximately 200 to 325 MBH. A Standard Model 400B-02P
(PROPANE) gas burner is shipped with a .180 diameter orifice installed for an input capacity
range of approximately 225 to 260 MBH. If the required rate does not fall within the capacity
range of the installed spud, select the correct input capacity range from Table 3 and install the
spud with the correct orifice size (stamped with inch diameter) from the SPUD KIT bag. If the
required firing rate is at the minimum of a capacity range, select the next lower range spud.

TO CHANGE SPUD: Turn Manual Gas Cock Knob on Combination Valve to

OFF

. Remove

the Spud Holder. See Table 3, and Figure 6 or 7.

The Combination Valve Gas Pressure Regulator is set to provide 2.0" W.C. NATURAL (8.0"

W.C. PROPANE) manifold gas pressure for low to minimum spud capacity input. Both models
are shipped with the primary air controlling shutter set WIDE OPEN to provide a lean gas/air
mixture during the initial start-up. Do not change the Combination Valve Gas Pressure
Regulator setting at this time.

CAUTION: The approximate air and gas settings described above are for

initial start-up only. Final settings must be made in accordance with Section

VIII. Instructions for adjustment of the manifold gas pressure are detailed in

Section XI.

* Main Gas Spud Orifice
Size, approximate
Manifold Pressure.

Data shown is approxi-
mate and based on "0"
overfire pressure at sea
level.

6

VII Main Gas Spud

Figure 6: Piping Connections

Table 3

:

Main Gas Spud Capacity and Preliminary Gas

and Air Settings

VI Piping Continued

Summary of Contents for Economite 400B-02 Series

Page 1: ...tion equipment and remove such hazards Affix this manual adjacent to the conversion burner CODE COMPLIANCE IS THE SOLE RESPONSIBILITY OF THE INSTALLER WARNING If the information in these instructions...

Page 2: ...g provision must be made for an outside air supply near the gas utilization equipment area Install permanently open grilles sized at not less than one square inch free area per 4 000 BTU of burner inp...

Page 3: ...NG Burner cabinet must be mounted in orientation shown in figures 1 and 2 Any other mountings may cause a dangerous condition and will void burner warranty and agency approvals Non standard arrangemen...

Page 4: ...rsely affect burner operation or if flue gas spillage might introduce a hazard If such a device is used it shall be of the listed type and installed and adjusted by a qual ified service technician in...

Page 5: ...of 5 0 W C pressure 11 0 W C PROPANE to the inlet of the Combination Valve when the burner and all other gas utilization equipment are on Note If there is more than 1 0 W C differential in the inlet p...

Page 6: ...and install the spud with the correct orifice size stamped with inch diameter from the SPUD KIT bag If the required firing rate is at the minimum of a capacity range select the next lower range spud...

Page 7: ...ustment 8 Turn operating control to ON or set thermostat above room temperature Main flame should come on when the motor reaches operating speed If not refer to Trouble Chart To make a preliminary set...

Page 8: ...C for NATUR AL gas 8 0 W C for PROPANE 1 Standby gas pressure inches W C 2 The efficiency of the thermocouple and the pilotstat safety control can be determined by timing the safety shut off With the...

Page 9: ...te and electrical interlock switch so as to prevent the burner from firing if the Blower Wheel is not running at its operat ing speed When the motor is off the actuator spring forces the disk against...

Page 10: ...u 5 for the method of isolating the problem If on a call for heat the main burner fails to operate even though the pilot is burning and the motor is running failure of the electric valve operator s ma...

Page 11: ...t flame gas pressure See Section IX Venturi Casting and Pilot E Clogged pilot orifice s See Section IX Venturi Casting and Pilot F Defective ignitor ignitor wires spark rod or improper spark gap See F...

Page 12: ...ent closed too far D Dirty Blower Wheel A Electric Valve Operator s of Combination Valve is defective and entire valve must be replaced Normal low voltage Motor running 24V minimum Combination Valve e...

Reviews: