Maintenance Continued

LIGHTING INSTRUCTIONS:

1. SET OPERATING CONTROL TO 

OFF

OR THERMOSTAT BELOW ROOM

TEMPERATURE.

2. TURN MANUAL GAS COCK KNOB ON COMBINATION VALVE TO ON
3. TURN BURNER POWER 

ON

.

4. SET OPERATING CONTROL TO 

ON

OR THERMOSTAT TO CALL FOR HEAT.

5. WAIT 6 SECONDS.  IF BURNER HAS FAILED TO LIGHT, OR IF BURNER LIGHTS

THEN GOES OUT AND SYSTEM GOES INTO SAFETY LOCKOUT, DE-ENERGIZE
THE SYSTEM BY SETTING OPERATING CONTROL TO 

OFF

OR THERMOSTAT

BELOW ROOM TEMPERATURE FOR AT LEAST 30 SECONDS TO RESET THE
SYSTEM AND THEN SET OPERATING CONTROL TO 

ON

OR THERMOSTAT TO

CALL FOR HEAT.

TO SHUT OFF

1. TURN MANUAL GAS COCK KNOB ON COMBINATION VALVE TO 

OFF

.

2. TURN BURNER POWER 

OFF

.

SHOULD OVERHEATING OF THE GAS UTILIZATION EQUIPMENT OCCUR:

1. Shut off the Main Manual Shut-off Valve to the  equipment.
2.

Do not

shut off the power switch to the 

ECONOMITE

burner, or to the equipment pump

or blower.

WARNING: If PROPANE gas is used and the burner is located in a basement,

crawl space or confining space, contact your gas supplier about installing a GAS LEAK
warning device. PROPANE gas is heavier than air and can settle in low areas or con-
fined spaces.  This would create a danger of explosion or fire.  If you suspect a gas
leak, follow instructions on front of this manual.

Make sure the thermostat and operating controls are calling for heat.  Defective wiring or loose
connections can simulate the component defects outlined below.  Check associated wiring
before replacing a component.

ELECTRICAL AND FLAME CHECKS MUST BE MADE IN THE ORDER LISTED.

I. MOTOR WILL NOT RUN OR MOTOR RUNS IN REPEATED CYCLES.

A. Confirm 120V between strip terminals 1 and 2 and verify the circuit polarity and

electrical ground, between strip terminal 1 and GND.

B. Check 24V* operating control circuit:

1. Between left strip terminal T and GND.

a. No voltage, transformer defective
b. Very low voltage,* circuit overloaded or transformer defective.

2. Between right strip terminal T and GND. No voltage, circuit between T and T is open.

C. Confirm 120V between strip terminal 2 and motor relay terminal 4:

1. No voltage, motor relay is defective.
2. Voltage present, motor is defective.

II. MOTOR RUNS CONTINUOUSLY, BUT NO FLAME.

A. Confirm that both Main Manual Shut-Off and Combination Gas Shut-Off valves are in

the ON position.

B. Whenever the burner fails to light during the 6-second ignition try, or if the flame is

lost during the burner run and not re-established within 6 seconds, the Electronic
Control will shut off the combination valve and lock out.  To reset the Control for
restart, set the operating control to OFF or thermostat below room temperature
for at least 30 seconds.
1. Check for 24V* between the Interlock Switch NC terminal and strip terminal GND.

No voltage, blower interlock circuit is defective.  See Section X.

2. If Electronic Control has a fuse, test for 24V* from each end of fuse to strip

terminal GND.

C. For each of the following tests, reset the Electronic Control per step II.B.  TESTS

ARE VALID ONLY DURING THE 6 SECOND TRIAL FOR IGNITION.
1. TURN THE MANUAL GAS COCK VALVE OFF. Check for 24V* between the

Electronic Control VALVE terminal and strip terminal GND.  No voltage,
defective Electronic Control.

Consumer Instructions

11

Trouble Chart

Trouble Chart

Consumer Instruction

Continued

Summary of Contents for Economite DS45B

Page 1: ...any other appli ance Installation and service must be per formed by a qualified installer service agency or the gas supplier WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas suppliers instructions If you cannot reach your gas supplier call ...

Page 2: ...ular air ducts shall not be less than 3 inches In Canada for detailed ventilation requirements refer to standard CAN 1 B149 1 or 2 and or local codes ______________________________________________________ Clean the gas utilization equipment combustion chamber heat exchanger interior and flue connections Remove all adhering tars scale dirt and soot Inspect for actual leaks and or potential leaks Ce...

Page 3: ... the burner tube is too short to reach the combustion chamber such as old fashioned gravity warm air furnace installations WARNING Burner cabinet must be mounted in orientation shown in Figures 1 and 2 Any other mountings may cause a dangerous condition and will void burner warranty and agency approvals Non standard arrangements may be available for some models consult factory for details if requi...

Page 4: ...y In no case shall the relief opening of the draft hood or barometric draft regulator be located at a point lower than the top of the highest flue passage in the equipment Gas utilization equipment requiring controlled draft may be equipped with a listed double acting barometric draft regulator installed and adjusted in accordance with the manufacturer s instructions if approved by local codes A d...

Page 5: ...igure 5 The burner gas supply piping should branch off from the main line as close to the gas meter as possible Do not connect to the bottom of a horizontal section Use new black pipe and malleable fittings free of cutting and threading burrs or defects Provide a sediment trap union and 1 8 pressure tap in piping close to burner as shown in Figure 5 Use pipe joint compound resistant to Liquid Petr...

Page 6: ...apacity spud input The burner is shipped with the primary air controlling shutter set wide open to provide a lean gas air mixture during the initial start up Do not change the combination gas valve pressure regulator setting at this time CAUTION The approximate air and gas settings described above are for initial start up only Final settings must be made in accordance with Section VIII Instruction...

Page 7: ...lization equipment must be off Then Divide by 1 000 for MBH value For PROPANE gas consult your supplier for method of determining firing rate 10 Readjust the primary air shutter to provide a quiet soft blue flame with well defined orange and yellow tips for NATURAL gas or with well defined yellow tips for PROPANE gas 11 Check the operation of the burner start and stop it several times with the the...

Page 8: ...set to its original position following servicing Cleaning of the blower wheel is usually the only service required Need for cleaning is indicated if the air cage assembly shows an accumulation of dust and lint or if the character of the flame indicates a deficiency of air Motor cooling air vents should also be cleaned at this time The blower side plate motor and wheel are removed as an assembly Di...

Page 9: ...ld gas pressure of 3 5 W C for NATURAL If pressure adjustment is required for setting capacity remove regulator cap for access to slotted adjustment screw Turning of adjustment screw counter clockwise reduces pressure clockwise increases pressure Do not adjust past the point where no change in pressure is noted NOTE Pressure setting must be made with burner running and main gas ON CAUTION When adj...

Page 10: ...Do not use this device if it gets wet It can malfunction and cause serious injury or death Replace any device that has been wet ______________________________________________________ Keep the area around the burner clear and free of combustible materials gasoline or other flammable liquids or vapors Do not obstruct burner air openings or ventilation grills for combustion air The motor features per...

Page 11: ...ER LISTED I MOTOR WILL NOT RUN OR MOTOR RUNS IN REPEATED CYCLES A Confirm 120V between strip terminals 1 and 2 and verify the circuit polarity and electrical ground between strip terminal 1 and GND B Check 24V operating control circuit 1 Between left strip terminal T and GND a No voltage transformer defective b Very low voltage circuit overloaded or transformer defective 2 Between right strip term...

Page 12: ...d steady Verify per Section VII that the spud orifice size and manifold pressure are correct b Zero erratic low or high pressure confirm that the inlet pressure to the combination valve is between 5 0 and 14 0 W C for NATURAL 11 0 to 14 0 W C PROPANE during standby and during trial for ignition c If manifold pressure is zero below 1 5 or above 3 5 W C NATURAL 10 0 W C PROPANE or erratic replace co...