background image

12

Midco International Inc.

4140 West Victoria Street * Chicago, Illinois 60646

tel  773.604.8700    fax  773.604.4070    web   www.midco-intl.com   email  sales@midco-intl.com

2. Check for 24V* between valve TH (PWR) terminal and valve body:

a. With voltage, reset Electronic Control and listen for audible CLICK as first

valve operator opens.  No CLICK, replace valve.

3. Check for ignition spark (spark length approximately  1/8"). Since this is a

capacitor discharge system, observe closely when visually checking the spark as
it is faint and thread-like and may be overlooked in bright light.
a. Between Electronic Control high voltage terminal and strip terminal GND.  No

spark, defective  Electronic Control.

b. Between Electronic Control high voltage terminal and Spark Electrode Wire

(insert head of #8x3/4" or longer round head screw into terminal wire). No
spark, broken wire or cracked insulator, or "spark gap" too wide (see Section
IX).

c. Between electrode tip and top of ground rod (see Figure 7).  If electrode tip is

not visible but spark can be heard continue with test II.C.4.

d. If spark is not heard, remove drawer assembly (see Section IX) and ground it

solidly to burner metal.  Repeat test c. above.

4. TURN MANUAL GAS COCK KNOB ON.  Connect manometer to the manifold gas
pressure tap and, during trial for ignition, check the gas pressure:

a. Pressure should be between 1.5" and 3.5" W.C. NATURAL (10.0 W.C."

PROPANE), and steady.  Verify per Section VII that the spud orifice size and
manifold pressure are correct.

b. Zero, erratic, low or high pressure:  confirm that the inlet pressure to the

combination valve is between 5.0" and 14.0" W.C. for NATURAL (11.0" to
14.0"  W.C. PROPANE), during standby and during trial for ignition.

c. If manifold pressure is zero, below 1.5" or above  3.5" W.C. NATURAL (10.0"

W.C. PROPANE) or erratic, replace combination valve.

III. FLAME ON ONLY DURING 6-SECOND TRIAL FOR IGNITION.

A. With motor running check burner line voltage terminals  for 120V as follows:

1. Between strip terminals 1 and 2 - 120V; voltage OK.
2. Between strip terminals 1 and GND - 120V; ground OK.
3. Between strip terminals 2 and GND -"0"V; no backfeed OK.

B. Follow reset procedure as specified in step II.B.

1. Check flame rod position per Figure 7.
2. Check sensor wire for continuity.
3. Connect DC microammeter in series Electronic Control SENSE terminal and

sensor wire.  With flame on, flame signal should be at least 2 microamps.

C. IMPORTANT: If changes are made in the Main Spud Orifice size, Manifold Gas

Pressure or Primary Air Adjustment, change the installation data tag accordingly.

IV. SHORT FLAME.

A. Low gas pressure.
B. Primary air adjustment open too far.
C. Main spud orifice too small.

V. LONG HAZY FLAME.

A. High gas pressure.
B. Primary air adjustment closed too far.
C. Dirty blower wheel.
D. Main spud orifice too large.

VI. GAS FAILS TO SHUT OFF.

A. Defective combination valve.

* Normal low voltage:

Motor running - 24V minimum.
Combination valve energized - 21V minimum.   

Trouble Chart

Trouble Chart 

Continued

1207

8470 72

Printed in USA

Summary of Contents for Economite DS45B

Page 1: ...any other appli ance Installation and service must be per formed by a qualified installer service agency or the gas supplier WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas suppliers instructions If you cannot reach your gas supplier call ...

Page 2: ...ular air ducts shall not be less than 3 inches In Canada for detailed ventilation requirements refer to standard CAN 1 B149 1 or 2 and or local codes ______________________________________________________ Clean the gas utilization equipment combustion chamber heat exchanger interior and flue connections Remove all adhering tars scale dirt and soot Inspect for actual leaks and or potential leaks Ce...

Page 3: ... the burner tube is too short to reach the combustion chamber such as old fashioned gravity warm air furnace installations WARNING Burner cabinet must be mounted in orientation shown in Figures 1 and 2 Any other mountings may cause a dangerous condition and will void burner warranty and agency approvals Non standard arrangements may be available for some models consult factory for details if requi...

Page 4: ...y In no case shall the relief opening of the draft hood or barometric draft regulator be located at a point lower than the top of the highest flue passage in the equipment Gas utilization equipment requiring controlled draft may be equipped with a listed double acting barometric draft regulator installed and adjusted in accordance with the manufacturer s instructions if approved by local codes A d...

Page 5: ...igure 5 The burner gas supply piping should branch off from the main line as close to the gas meter as possible Do not connect to the bottom of a horizontal section Use new black pipe and malleable fittings free of cutting and threading burrs or defects Provide a sediment trap union and 1 8 pressure tap in piping close to burner as shown in Figure 5 Use pipe joint compound resistant to Liquid Petr...

Page 6: ...apacity spud input The burner is shipped with the primary air controlling shutter set wide open to provide a lean gas air mixture during the initial start up Do not change the combination gas valve pressure regulator setting at this time CAUTION The approximate air and gas settings described above are for initial start up only Final settings must be made in accordance with Section VIII Instruction...

Page 7: ...lization equipment must be off Then Divide by 1 000 for MBH value For PROPANE gas consult your supplier for method of determining firing rate 10 Readjust the primary air shutter to provide a quiet soft blue flame with well defined orange and yellow tips for NATURAL gas or with well defined yellow tips for PROPANE gas 11 Check the operation of the burner start and stop it several times with the the...

Page 8: ...set to its original position following servicing Cleaning of the blower wheel is usually the only service required Need for cleaning is indicated if the air cage assembly shows an accumulation of dust and lint or if the character of the flame indicates a deficiency of air Motor cooling air vents should also be cleaned at this time The blower side plate motor and wheel are removed as an assembly Di...

Page 9: ...ld gas pressure of 3 5 W C for NATURAL If pressure adjustment is required for setting capacity remove regulator cap for access to slotted adjustment screw Turning of adjustment screw counter clockwise reduces pressure clockwise increases pressure Do not adjust past the point where no change in pressure is noted NOTE Pressure setting must be made with burner running and main gas ON CAUTION When adj...

Page 10: ...Do not use this device if it gets wet It can malfunction and cause serious injury or death Replace any device that has been wet ______________________________________________________ Keep the area around the burner clear and free of combustible materials gasoline or other flammable liquids or vapors Do not obstruct burner air openings or ventilation grills for combustion air The motor features per...

Page 11: ...ER LISTED I MOTOR WILL NOT RUN OR MOTOR RUNS IN REPEATED CYCLES A Confirm 120V between strip terminals 1 and 2 and verify the circuit polarity and electrical ground between strip terminal 1 and GND B Check 24V operating control circuit 1 Between left strip terminal T and GND a No voltage transformer defective b Very low voltage circuit overloaded or transformer defective 2 Between right strip term...

Page 12: ...d steady Verify per Section VII that the spud orifice size and manifold pressure are correct b Zero erratic low or high pressure confirm that the inlet pressure to the combination valve is between 5 0 and 14 0 W C for NATURAL 11 0 to 14 0 W C PROPANE during standby and during trial for ignition c If manifold pressure is zero below 1 5 or above 3 5 W C NATURAL 10 0 W C PROPANE or erratic replace co...

Reviews: