background image

V Electrical 

The length of horizontal uninsulated Vent Connector between chimney and a single gas

utilization equipment shall not exceed 75% of the height of the chimney above the
connector, or 100% if the Vent Connector is insulated.

The Vent Connector shall be installed so as to avoid turns or other construction features

which create excessive resistance to flow of vent gas.  It shall be installed without any dips
or sags and shall slope upward at least  1/4" per foot.

A manually operated damper shall 

not

be placed in the Vent Connector or chimney of

any gas utilization equipment.

The Vent Connector shall be firmly attached to draft hood outlets and flue collars.  Joints

between sections of connector piping shall be fastened by sheet-metal screws or other
approved means.  The Vent Connector shall be supported for the design and weight of the
material employed to maintain clearance and prevent physical damage and separation of
joints.

A draft hood or a barometric draft regulator shall be installed in the same room or

enclosure as the equipment in such a manner as to prevent any difference in the pressure
between the hood or regulator and the combustion air
supply.  In no case shall the relief opening of the draft hood
or barometric draft regulator be located at a point lower than
the top of the highest flue   passage in the equipment.

Gas utilization equipment requiring controlled draft may

be equipped with a listed double acting barometric draft
regulator, installed and adjusted in accordance with the
manufacturer’s instructions, 

if approved by local codes

.

A device which will automatically shut off gas to the

burner in the event of sustained backdraft is required. It
shall be of the listed manual reset type and installed and
adjusted by a qualified service technician in accordance
with the manufacturer’s instructions.

______________________________________________________

Installation wiring and grounding of the burner must conform to local codes, or, in their
absence in the United States to 

National Electric Code, ANSI/NFPA No. 70

- latest edition;

in Canada, to 

Canadian Electrical Code Part 1, CSA Standard C22.1

.

Use copper wire not less than 14 gage for line voltage wiring.  Be sure to hook up to

permanently live circuit.  Provide a fused on-off disconnect switch carrying a minimum 3
amp fuse.

4

Part 1 Installation

Part 1

Installation 

Continued 

IV Chimney, Vent 

Connector*, and 

Draft Control 

Continued 

250 MBH

320 MBH

400 MBH

7”

8”

9”

Maximum

Input

Flue Pipe

Diameter

Table 1:

Recommended

Vent Connector Sizes

Figure 4:

Wiring Diagram

Summary of Contents for Economite DS45B

Page 1: ...any other appli ance Installation and service must be per formed by a qualified installer service agency or the gas supplier WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas suppliers instructions If you cannot reach your gas supplier call ...

Page 2: ...ular air ducts shall not be less than 3 inches In Canada for detailed ventilation requirements refer to standard CAN 1 B149 1 or 2 and or local codes ______________________________________________________ Clean the gas utilization equipment combustion chamber heat exchanger interior and flue connections Remove all adhering tars scale dirt and soot Inspect for actual leaks and or potential leaks Ce...

Page 3: ... the burner tube is too short to reach the combustion chamber such as old fashioned gravity warm air furnace installations WARNING Burner cabinet must be mounted in orientation shown in Figures 1 and 2 Any other mountings may cause a dangerous condition and will void burner warranty and agency approvals Non standard arrangements may be available for some models consult factory for details if requi...

Page 4: ...y In no case shall the relief opening of the draft hood or barometric draft regulator be located at a point lower than the top of the highest flue passage in the equipment Gas utilization equipment requiring controlled draft may be equipped with a listed double acting barometric draft regulator installed and adjusted in accordance with the manufacturer s instructions if approved by local codes A d...

Page 5: ...igure 5 The burner gas supply piping should branch off from the main line as close to the gas meter as possible Do not connect to the bottom of a horizontal section Use new black pipe and malleable fittings free of cutting and threading burrs or defects Provide a sediment trap union and 1 8 pressure tap in piping close to burner as shown in Figure 5 Use pipe joint compound resistant to Liquid Petr...

Page 6: ...apacity spud input The burner is shipped with the primary air controlling shutter set wide open to provide a lean gas air mixture during the initial start up Do not change the combination gas valve pressure regulator setting at this time CAUTION The approximate air and gas settings described above are for initial start up only Final settings must be made in accordance with Section VIII Instruction...

Page 7: ...lization equipment must be off Then Divide by 1 000 for MBH value For PROPANE gas consult your supplier for method of determining firing rate 10 Readjust the primary air shutter to provide a quiet soft blue flame with well defined orange and yellow tips for NATURAL gas or with well defined yellow tips for PROPANE gas 11 Check the operation of the burner start and stop it several times with the the...

Page 8: ...set to its original position following servicing Cleaning of the blower wheel is usually the only service required Need for cleaning is indicated if the air cage assembly shows an accumulation of dust and lint or if the character of the flame indicates a deficiency of air Motor cooling air vents should also be cleaned at this time The blower side plate motor and wheel are removed as an assembly Di...

Page 9: ...ld gas pressure of 3 5 W C for NATURAL If pressure adjustment is required for setting capacity remove regulator cap for access to slotted adjustment screw Turning of adjustment screw counter clockwise reduces pressure clockwise increases pressure Do not adjust past the point where no change in pressure is noted NOTE Pressure setting must be made with burner running and main gas ON CAUTION When adj...

Page 10: ...Do not use this device if it gets wet It can malfunction and cause serious injury or death Replace any device that has been wet ______________________________________________________ Keep the area around the burner clear and free of combustible materials gasoline or other flammable liquids or vapors Do not obstruct burner air openings or ventilation grills for combustion air The motor features per...

Page 11: ...ER LISTED I MOTOR WILL NOT RUN OR MOTOR RUNS IN REPEATED CYCLES A Confirm 120V between strip terminals 1 and 2 and verify the circuit polarity and electrical ground between strip terminal 1 and GND B Check 24V operating control circuit 1 Between left strip terminal T and GND a No voltage transformer defective b Very low voltage circuit overloaded or transformer defective 2 Between right strip term...

Page 12: ...d steady Verify per Section VII that the spud orifice size and manifold pressure are correct b Zero erratic low or high pressure confirm that the inlet pressure to the combination valve is between 5 0 and 14 0 W C for NATURAL 11 0 to 14 0 W C PROPANE during standby and during trial for ignition c If manifold pressure is zero below 1 5 or above 3 5 W C NATURAL 10 0 W C PROPANE or erratic replace co...

Reviews: