background image

SPUD
DRILL

SIZE

25/64

(.390)

7/16

3

(.437)

SPUD

RE-

MOVED

BURNER

INPUT

MBH

1

300
400

400
540

540
625
700

MANIFOLD

PRESSURE

W.C.

2

2.0"
3.5"

2.0"
4.0"

1.85"

2.5"
3.2"

SPUD
DRILL

SIZE

#9 (.196)
#3 (.213)

#1 (.228)

17/64 

(.265)

9/32

(.281)

19/64

(.296)

BURNER

INPUT

MBH

1

300
350

400
540

625
700

MANIFOLD

PRESSURE

W.C.

2

10.0"

NATURAL GAS

PROPANE GAS

DATA IS APPROXIMATE AND BASED ON "0"

OVERFIRE PRESSURE AT SEA LEVEL OVERFIRE

TABLE 2: 

Spud Capacity and Preliminary Gas Settings

1.

Input range of spud. Adjust the main regulator to vary the
manifold  gas pressure  and burner input within the range
shown for a specific spud drill size. With PROPANE, do not
exceed 11.0" W.C. under any circumstances.

2.

Approximate gas pressure at manifold gas pressure tap.

3.

Drill out 25/64 spare spud to 7/16.

VIII  INITIAL START-UP/ADJUSTMENT

WARNING: Ignition is automatic. Make spark

observations into combustion chamber only with
Main and Pilot Manual Shut-Off Valves closed.
Confirm that gas utilization equipment does not
contain any accumulated gases. Purge as described
in step 3 below.
1.

Check the burner piping and valves for gas leaks by
applying a  weak  liquid soap solution to unions and
joints   with  the  gas  supply  on.  Leakage  will  be
indicated by the appearance of soap bubbles. Locate
and correct all gas leaks before proceeding.
WARNING: DO NOT USE OPEN FLAME.

2.

Purging the air from the gas supply line at this  step
will expedite first light-off.

IMPORTANT: Purge outside the building.
Do not purge into the gas utilization equipment.

3.

To purge the gas utilization equipment and chimney
of any accumulated  gases, turn Manual Gas  Cock
Knob  on  Combination  Valve  to  OFF,  close Pilot
Manual Shut-Off Valve,  turn burner power on,  and
set operating control to ON or thermostat to call  for
heat. Let the blower run long enough to accomplish
four air changes, but not less than five minutes.

4.

IMPORTANT:Make sure that the capacity range of
the  installed spud and the  preliminary  combustion
air  shutter setting are suitable for capacity rating of
the gas utilization  equipment.  Refer to Section VII 
and Table 2. 

5.

RESET

the  Electronic   Control   by   setting   the

operating  control  to  OFF  or the thermostat below
room  temperature  for  at  least  30  seconds.  See
Section XII.

6.

Confirm  that Main and Pilot Manual Shut-Off Valves
are    open.  Turn   Manual   Gas   Cock   Knob  on
Combination Valve to ON.

7.

Turn operating control to ON or set thermostat above
room temperature. After a 30 second  pre-purge,  the
pilot should ignite. Whenever the burner pilot fails to
light  during  the  15-second  ignition  trial,  or  if the
flame   is   lost   during   the   burner  run and is not
re-established within 15 seconds after the pre-purge,
the  Electronic  Control will shut off the Combination
Valve  and  LOCK  OUT. To RESET  the Electronic
Control for restart, de-energize the Electronic Control
by setting the operating control to OFF or thermostat
below room temperature for at least 30 seconds.  If 
burner  still  fails  to  light, turn it off and repeat from
step  5  above.   Then  if   necessary,   refer  to  the
TROUBLE CHART to isolate the problem.

WARNING:  Repeated unsuccessful attempts

to  light will  result in accumulated gases in gas
utilization equipment and  chimney.  To  prevent
these  gases  from  reaching  an explosive level,
periodically purge the gas utilization  equipment
and chimney as described in step 3 above.

CONSTRUCTION MAY VARY BY BURNER APPLICATION REQUIREMENTS

FIGURE 5 

Piping Connections

-5-

Summary of Contents for ECONOMITE F400B-33

Page 1: ...s or in the absence of local codes with Installation of Domestic Gas Conversion Burners ANSI Z21 8b 1993 and National Fuel Gas Code ANSI Z223 1 1992 or latest edition s available from American Nationa...

Page 2: ...is of one square inch free area per 1 000 BTU of the total input rating of all gas utilization equipment in the combined space One grille should be located within 12 inches of the ceiling the other wi...

Page 3: ...at transfer to the primary surfaces of the heat exchanger In most cases the existing combustion chamber liner formerly used for oil burner can be used if in good condition In the case of wet base boil...

Page 4: ...ing close to burner as shown in Figure 5 Use pipe joint compound approved for use with Liquid Petroleum Gases Piping must comply with local codes To obtain the maximum firing rate of 700 MBH the NATUR...

Page 5: ...bination Valve to OFF close Pilot Manual Shut Off Valve turn burner power on and set operating control to ON or thermostat to call for heat Let the blower run long enough to accomplish four air change...

Page 6: ...r Switch are turned OFF before removing any parts for service WARNING All cover plates enclosed and guards must be in place at all times except during maintenance and servicing IX PILOT The pilot is o...

Page 7: ...e switch plunger to push it past its operating point When running the actuator pulls the disk clear of the plunger To make a specific test of the interlock circuit 1 Turn burner power OFF 2 Turn Manua...

Page 8: ...justable for outlet pressure range of 2 0 W C to 5 0 W C Outlet pressure settings must be checked while the gas is flowing To adjust outlet pressure remove the seal cap for access to the adjusting scr...

Page 9: ...D AND THE BURNER IS LOCATED IN A BASEMENT CRAWL SPACE OR CONFINING SPACE CONTACT YOUR GAS SUPPLIER ABOUT INSTALLING A GAS LEAK WARNING DEVICE PROPANE GAS IS HEAVIER THAN AIR AND CAN SETTLE IN LOW AREA...

Reviews: