XI REDUNDANT COMBINATION GAS

VALVE

The Combination Valve contains a Manual Gas Shut-Off,
Main Gas Pressure Regulator, and Automatic Electric
Main Gas Valve.

The Combination Gas Valve is suitable for a maximum

pressure of 14.0" W.C. 

When the gas supply pressure is over 14.0" W.C.,

special regulators are required. See Section VI Piping.

Should replacement or service be required, valve

manufacturer's instructions must be followed as outlined
in their information sheet.

The Main Gas Pressure Regulator is adjustable for

outlet pressure range of 2.0" W.C. to 5.0" W.C.

Outlet pressure settings must be checked while the

gas is flowing.

To adjust outlet pressure, remove the seal cap for

access to the adjusting screw. Turning the screw
clockwise will increase outlet pressure, counter
clockwise will decrease outlet pressure.

XII S8680J ELECTRONIC CONTROL

For operation characteristics refer to Honeywell

Control literature provided with burner.

XIII

SPECIAL EQUIPMENT (OEM
VERSIONS)

Special equipment, either factory or contractor

installed, may cause variation in the procedures and
descriptions given in this manual.

Consult the OEM's manual to identify the differences in
the information.

FIGURE 7 

General Assembly

-8-

Summary of Contents for ECONOMITE F400B-33

Page 1: ...s or in the absence of local codes with Installation of Domestic Gas Conversion Burners ANSI Z21 8b 1993 and National Fuel Gas Code ANSI Z223 1 1992 or latest edition s available from American Nationa...

Page 2: ...is of one square inch free area per 1 000 BTU of the total input rating of all gas utilization equipment in the combined space One grille should be located within 12 inches of the ceiling the other wi...

Page 3: ...at transfer to the primary surfaces of the heat exchanger In most cases the existing combustion chamber liner formerly used for oil burner can be used if in good condition In the case of wet base boil...

Page 4: ...ing close to burner as shown in Figure 5 Use pipe joint compound approved for use with Liquid Petroleum Gases Piping must comply with local codes To obtain the maximum firing rate of 700 MBH the NATUR...

Page 5: ...bination Valve to OFF close Pilot Manual Shut Off Valve turn burner power on and set operating control to ON or thermostat to call for heat Let the blower run long enough to accomplish four air change...

Page 6: ...r Switch are turned OFF before removing any parts for service WARNING All cover plates enclosed and guards must be in place at all times except during maintenance and servicing IX PILOT The pilot is o...

Page 7: ...e switch plunger to push it past its operating point When running the actuator pulls the disk clear of the plunger To make a specific test of the interlock circuit 1 Turn burner power OFF 2 Turn Manua...

Page 8: ...justable for outlet pressure range of 2 0 W C to 5 0 W C Outlet pressure settings must be checked while the gas is flowing To adjust outlet pressure remove the seal cap for access to the adjusting scr...

Page 9: ...D AND THE BURNER IS LOCATED IN A BASEMENT CRAWL SPACE OR CONFINING SPACE CONTACT YOUR GAS SUPPLIER ABOUT INSTALLING A GAS LEAK WARNING DEVICE PROPANE GAS IS HEAVIER THAN AIR AND CAN SETTLE IN LOW AREA...

Reviews: