background image

Midco International Inc. 

11

8471 15

MADE

 in the 

USA

Trouble Chart

Make  sure  the  thermostat  and  operating  controls  are  calling  for  heat.  Defective  wiring  or  loose 
connections  can  simulate  the  component  defects  outlined  below.  Check  associated  wiring  before 
replacing a component.

ELECTRICAL AND FLAME CHECKS MUST BE MADE IN THE ORDER LISTED

.

I. 

MOTOR WILL NOT RUN

A. Confi rm 120V between strip terminals:

1. 

L2

 & 

L1

 no voltage - Fused disconnect off  or Fuse open.

2. 

L2

 & 

3

 no voltage - Optional on/off  and/or safety controls open.

3. 

L2

 & 

4

 no voltage - Burner Switch or Timer open and/or Remote Switch or Timer open.

4. 

L2

 & Thermal Switch terminal 1 (black wire).

a. None - Thermal Switch is defective.
b. Yes - Motor is defective.

II. 

MOTOR RUNS CONTINUOUSLY, BUT NO FLAME- HOUSING COOL

A. Confi rm that Main Manual Shut-Off  Valve is open.
B. Check for 120V between strip terminals 

4

 and 

L2

.

1. Yes - turn Burner Switch or Timer off  for a minimum, of 30 seconds to 

RESET

 Electronic

Control.
2. No voltage, Thermal Switch is defective.

C. Check for 24V* between strip terminals 

6

 to 

10

. No voltage, transformer is defective.

D. Check for 24V* between strip terminals 

5

 and 

10

. No voltage, motor interlock switch is defective.

E. Check for 24V* between Electronic Control 

24 (PWR)

 terminal and strip terminal 

10

. 24V yellow 

wire from strip terminal 10 is defective.
F. Check for 24V* between Electronic Control 

24 (GND)

 terminal and strip terminal 

10

. No voltage, 

red wire from terminal strip 5 is defective.
G. Turn burner control off  for a minimum of 30 seconds to 

RESET

 Electronic Control for each of the 

following steps.

 

 

CAUTION: Tests are valid only during the 6 second trial for ignition

.

1. Check for 24V* between Electronic Control Valve terminal and strip terminal 

10

. No volt age, 

Electronic Control or Fuse is defective.
2. Check for 24V* between strip terminals 

7

 and 

10

. No voltage, blue wire from strip terminal 

7

 

is defective.
3. Check for ignition spark (spark length approximately 1/8″):

a. Between Electronic Control HI VOLTAGE terminal and earth ground. No spark, Electronic 
Control or Fuse is defective.
b. Between electrode wire and Spark Electrode. No Spark, Electrode wire is defective.
c. Check for spark between Spark Electrode and ground barrier. See Figure 5. If ignitor tip is 
not visible with burner mounted, but spark can be heard, continue with Step G4. If spark cannot 
be heard, refer to Section VIII IGNITOR AND REGULATOR ASSEMBLY for spark test.

4. Connect manometer to Ignitor Gas Pressures Test Tap and, during 6 second trial for ignition 
period, check gas pressure.

a. No pressure, confi rm that pressure of at least 4″ W.C. is available at inlet of automatic gas 
valve (connect manometer to valve upstream tap) and repeat Step G4. If still no ignitor gas 
pressure, valve is defective.
b. Ignitor gas pressure 3″ to 4″ W.C., continue with Step G5.
c. .Adjust the ignitor regulator to 3.5″ W.C. while gas is fl owing.

5.  Open  charging  door,  make  sure  any 

Door  Open

  interlock  is  bypassed,  and  repeat  trial  for 

ignition.

a. With fl ame on, close charging door and check combustion chamber pressure, burner peep 
hole can be used for access to obtain approximate reading. Make sure sensing tube extends 
into the combustion chamber for at 6″. Pressure should be between 0″ and minus 0.5″ W.C. If 
pressure is on the high negative side of the range, increase the ignitor gas pressure to 4″ or 
5″ W.C.
b.  No  fl ame,  clean  and  test  ignitor  assembly  per  Section  VIII  IGNITOR AND  REGULATOR 
ASSEMBLY

Trouble Shooting

Summary of Contents for J121-DS

Page 1: ...witch do not use any phone in your building Immediately phone your gas supplier from another building Follow the gas supplier s instructions If you cannot reach your gas supplier call the re departmen...

Page 2: ...d air at sea level with zero draft over re De rate burner for altitudes over 2 000 feet by 4 for each 1000 feet of additional elevation 4 100 MBH 100 000 BTU Hr No 1 Waste Primarily dry material such...

Page 3: ...MIDCO Accessory Weatherhood will provide such protection CAUTION If the incinerator is of the down draft design make sure that a direct draft vent opening of approximately 10 square inches has been p...

Page 4: ...en pressure testing the supply piping the burner valve train must be protected If the test pressure is 0 5 PSIG or less closing the Main Manual Shut O Valve will su ce CAUTION If the test pressure is...

Page 5: ...t these gases from reaching an explosive level periodically purge the incineration chamber as described in Step 5 9 Observe the ignitor ame If it is weak screw in the Ignitor regulator adjustment to i...

Page 6: ...Load incinerator and make trial run Con rm that the incineration chamber pressure stays within the range of 0 to minus 0 5 W C 16 WARNING When the incinerator is located inside a building and a draft...

Page 7: ...Midco International Inc 7 8471 15 MADE in the USA Part 1 Installation VII Initial Start Up Adjustment Continued Figure 2B Wiring diagram 6455 58 Figure 3 Control Components SCHEMATIC LEGEND...

Page 8: ...is no debris in the Blast Tube that could short out the Spark or Flame Electrode Clean the Ignitor Gas Ori ce in Tee Ori ce Fitting see Figure 5 and check that the ori ce size is correct per Table 3 C...

Page 9: ...nt screw __________________________________________ The valve is a single function on o type with automatic closing on current failure Replace entire valve if valve fails to open when power is applied...

Page 10: ...uring the burner run and not re established within 6 seconds the Control will shut o the Main Automatic Gas Valve and LOCK OUT To reset the Control for restart turn o the Burner Switch or Timer for at...

Page 11: ...trial for ignition 1 Check for 24V between Electronic Control Valve terminal and strip terminal 10 No volt age Electronic Control or Fuse is defective 2 Check for 24V between strip terminals 7 and 10...

Page 12: ...ls L2 and GND TERM no volt age no back feed neutral OK B Follow test procedure as speci ed in Step II G 1 Connect DC microamp meter in series with sense wire and Electronic Control SENSE terminal With...

Reviews: