Part 1 Installation

The supply piping to the burner should branch off  from the main line as close to the source as possible 
(NATURAL gas meter or PROPANE tank regulator). When branching off  from an existing gas line, 
do not tap off  the bottom of a horizontal section. Use new black pipe and malleable fi ttings free from 
cutting and threading burrs or defects.
-  Use  pipe  joint  compound  resistant  to  liquid  petroleum  gases  when  using  either  NATURAL  or 
PROPANE gas. Piping must comply with the local and national codes. If the burner piping must be 
rearranged  because  of  space  limitations,  be  sure  to  carry  out  the  general  confi guration  shown  in 
Figure 3.
- A suitable Main Gas Pressure Regulator should be installed as shown in Figures 1 or 2. Choose a 
regulator(s) to adjust the available gas pressure to the pressure shown in SPECIFICATIONS, page 2.
 

 

CAUTION: The regulated gas pressures must not exceed 14″ W.C. or Main Automatic 

Gas Valve and Ignitor Regulator will be damaged. If excessive gas pressure is prevalent, the 
regulator  must  be  a  tight  shut-off   type  to  prevent  high  pressures  from  developing  during 
stand-by.

- For full input, refer too SPECIFICATIONS, page 2, for minimum gas pressure required. For reduced 
capacities, refer to Firing Rate Curves, Table 2.
 

 

CAUTION: If gas supply pressure is below its specifi ed range during adjustment, an 

over-fi re condition could result when pressure returns to normal, particularly if the regulator 
adjustment screw is bottomed out. ALWAYS confi rm that at least the minimum rated pressure 
is being supplied during regulator adjustments, and NEVER BOTTOM OUT regulator screw.

 

-  When  selecting  the  burner  supply  piping  size  per  Table  1,  the  permissible  pressure  drop  must 
be  based  on  the  pressure  available  at  the  inlet  to  the  supply  pipe  branch  line  when  all  other  gas 
equipment fed by the same source (NATURAL gas meter or PROPANE tank regulator) is fi ring at full 
rate. Also take into account any other INCINOMITE burners to be attached to the same branch line.
- When pressure testing the supply piping, the burner valve train must be protected. If the test pressure 
is 0.5 PSIG or less, closing the Main Manual Shut-Off  Valve will suffi  ce.
 

 

CAUTION: If the test pressure is over 0.5 PSIG, the test must be made without any 

burner components connected, including Main Manual Shut-Off  Valves.

 

 

WARNING: EXPLOSION HAZARD. DO NOT USE OXYGEN FOR PRESSURE TESTING. 

AN EXPLOSION COULD OCCUR DURING INITIAL START-UP.

NPT  

TYPE          APPROXIMATE CAPACITY-MBH

PIPE 

OF 

            LENGTH OF PIPE / FEET

SIZE 

GAS 

 10 

20 

40 

60 

100

3/4″  

Natural   275 

200 

130 

100 

---

 

 

Propane  450 

300 

200 

165 

125

1″   

Natural   520 

350 

245 

195 

150

 

 

Propane  800 

550 

385 

300 

235

1 1/4″ 

Natural   800 

730 

500 

400 

300

 

 

Propane  --- 

800 

790 

630 

480

1 1/2″ 

Natural   --- 

800 

760 

610 

460

 

 

Propane  --- 

--- 

800 

800 

725

2″   

Natural   --- 

--- 

800 

800 

800

 

 

Propane  --- 

--- 

--- 

--- 

800

 

 

  

 

    __________________________________________

Installation wiring to the burner must conform to local codes, or, in their absence in the United States 
the  National  Electric  Code ANSI/NFPA  No.  70-  latest  edition;  in  Canada,  to  CSA  standard  C22.1, 
“Canadian Electrical Code Part 1.”
- Use copper wires and provide disconnect and fuse protection for each INCINOMITE installation. 
Refer  to  SPECIFICATIONS,  page  2,  for  ampacity.  Confi rm  that  the  polarity  is  correct—hot  wire  to 
strip terminal 

L1

, neutral 

L2

 and that the neutral line is not subject to induced low voltage (check 

L2 

to ground) from other equipment as that can aff ect the electronic control, causing it to malfunction.
- The frame of the burner should be well grounded. A terminal is provided in the control box for positive 
grounding.
 

 

CAUTION:  In  order  for  the  automatic  cooling  system  to  function,  power  must  be 

maintained to burner strip terminal L1. Do not install any safety or on-off  controls in the circuit 
between the fused disconnect switch and strip terminal L1. Optional remote control devices 
should be connected in place of, or in addition to, the switch or timer as indicted in Figure 2A 
or 2B Wiring Diagram.

 

 

  

 

    __________________________________________

V  Piping

Capacities shown are 

for total pressure drop 

of 0.3

W.C. For higher 

permissible pressure drops 

consult your fuel supplier.

Source:

 Gas Engineers

Handbook-1974

Industrial Press Inc. NY, NY

Table 1

 Schedule 40 Pipe Capacities in MBH

VI  Electrical

Summary of Contents for J121-DS

Page 1: ...witch do not use any phone in your building Immediately phone your gas supplier from another building Follow the gas supplier s instructions If you cannot reach your gas supplier call the re departmen...

Page 2: ...d air at sea level with zero draft over re De rate burner for altitudes over 2 000 feet by 4 for each 1000 feet of additional elevation 4 100 MBH 100 000 BTU Hr No 1 Waste Primarily dry material such...

Page 3: ...MIDCO Accessory Weatherhood will provide such protection CAUTION If the incinerator is of the down draft design make sure that a direct draft vent opening of approximately 10 square inches has been p...

Page 4: ...en pressure testing the supply piping the burner valve train must be protected If the test pressure is 0 5 PSIG or less closing the Main Manual Shut O Valve will su ce CAUTION If the test pressure is...

Page 5: ...t these gases from reaching an explosive level periodically purge the incineration chamber as described in Step 5 9 Observe the ignitor ame If it is weak screw in the Ignitor regulator adjustment to i...

Page 6: ...Load incinerator and make trial run Con rm that the incineration chamber pressure stays within the range of 0 to minus 0 5 W C 16 WARNING When the incinerator is located inside a building and a draft...

Page 7: ...Midco International Inc 7 8471 15 MADE in the USA Part 1 Installation VII Initial Start Up Adjustment Continued Figure 2B Wiring diagram 6455 58 Figure 3 Control Components SCHEMATIC LEGEND...

Page 8: ...is no debris in the Blast Tube that could short out the Spark or Flame Electrode Clean the Ignitor Gas Ori ce in Tee Ori ce Fitting see Figure 5 and check that the ori ce size is correct per Table 3 C...

Page 9: ...nt screw __________________________________________ The valve is a single function on o type with automatic closing on current failure Replace entire valve if valve fails to open when power is applied...

Page 10: ...uring the burner run and not re established within 6 seconds the Control will shut o the Main Automatic Gas Valve and LOCK OUT To reset the Control for restart turn o the Burner Switch or Timer for at...

Page 11: ...trial for ignition 1 Check for 24V between Electronic Control Valve terminal and strip terminal 10 No volt age Electronic Control or Fuse is defective 2 Check for 24V between strip terminals 7 and 10...

Page 12: ...ls L2 and GND TERM no volt age no back feed neutral OK B Follow test procedure as speci ed in Step II G 1 Connect DC microamp meter in series with sense wire and Electronic Control SENSE terminal With...