Page 4
GROUNDING AND BONDING (Continued)
Center Section
Center Section Bonding Studs
10-32 (2 Per Side)
Door
Bonding
Stud
1) Attach
backpan bonding wire
from 1/4”-20 backpan protective earth terminal (PET) to nearest
center section bonding stud (10-32) using hardware provided.
(FIGURE G)
NOTE:
The main protective earth ground needs to be the first terminal placed on the PET and this
terminal needs to be secured on its own with a nut. The bonding wire for the center section can
be added to the PET after securing the nut for the main ground.
(FIGURE G)
2) Attach
door bonding wire
(with male or female disconnect end) to door bonding stud with
nut (included).
(FIGURE G)
3) Attach remaining door bonding wire to nearest center section bonding stud (10-32) using hardware
provided.
(FIGURE G)
4) Connect male and female ends of door bonding wire set.
FIGURE G
FRONT VIEW
Door
Backpan
Backpan
PET Stud
SIDE VIEW