1 3
5
JP2
JP1
TEMPERATURE
A 3 position pluggable jumper (JP1, on circuit board)
is provided to adjust the temperature control range.
Mode 1
: The Fan speed is proportional to the factory-set temperature.
Mode 2
: Complete On (On or Off, is not proportional). This
mode is selected by removing a pluggable jumper on
the circuit board. (
FIGURE B
)
Remove for
Complete On Mode
TOP
Temperature
Setting
Jumper
Rear of
Circuit
Board
FIGURE B
SLOW
FULL SPEED
Position 3
Position 1
Position 5
90°
85°
80°
100°F
95°F (factory set)
90°F
SPECIFICATIONS
Power Input
: 120VAC - 60HZ
Power Output
: Fan cords (2 prong) outlets. Variable output,
30 to 120VAC @ 1 AMP
Protection
: 2 AMP fuse
CAUTION
: Disconnect the power by removing the plug before removing the fan control assembly.
ATTENTION
:
Débranchez l 'alimentation en retirant la fiche avant de retirer l' ensemble de commande
du ventilateur.
SETTINGS
• Remove the 2 nuts on unit’s mounting flange to access the jumpers on the module.
THERMOSTATIC PROPORTIONAL SPEED FAN CONTROLLER
Page 7
!
!