Page 4
PDCOOL-1120R
FRONT VIEW
REAR VIEW
PDCOOL-1120R CONNECTIONS, CONTROLS AND INDICATORS
POWER
ON
OFF
COMPONENT COOLER AND POWER DISTRIBUTION
PROTECTION
SURGE
1
1
2
3
4
5
2
3
4
50CFM BLOWER: This blower will turn on at 87° F (30.5° C) and run proportionately
(speed increases with temperature) from 87° F (30.5° C) to 95° F (35° C). At 95° F and above, the
blower will run at full speed. The blower will stop running at 85° F (29.4° C).
POWER SWITCH/20A CIRCUIT BREAKER WITH SWITCH GUARD.
TWO STAGE SURGE SUPPRESSION STATUS INDICATORS:
NEMA 5-20R POWER OUTLET.
C20 IEC POWER CORD INLET: 120V/60Hz power inlet. Plug supplied power cord from AC source
into this inlet.
6
GROUND/BOND STUD.
7
TEN NEMA 5-20R OUTLETS.
8
SURGE STATUS OUTPUT DRY CONTACT: This dry contact will close if both stage 1 and 2 surge is
compromised.
9
TEMPERATURE PROBE CONNECTION: 10 foot temperature probe provided.
6
5
7
8
9
Stage One Indicator Stage Two Indicator Status
On On Full Protection
Off On Stage One Compromised
Off Off Load Unprotected or Power Off
A blue LED will illuminate when the blower is receiving power.
120V - 60Hz - TOTAL 16A
120 VOLT
16 AMP
60 Hz