Chapter 4: Using the Command Line Interface
156
Configuring Environmental Sensors' Default Thresholds
You can set the default values of upper and lower thresholds, deassertion hysteresis and assertion timeout on a sensor
type basis, including temperature, humidity, air pressure and air flow sensors. The default thresholds automatically apply to
all environmental sensors that are newly detected or added.
A default threshold configuration command begins with
defaultThresholds
.
You can configure various default threshold settings for the same sensor type at a time by combining multiple commands.
See
Set the Default Upper Critical Threshold for a specific sensor type:
config:#
defaultThresholds <sensor type> upperCritical <value>
Set the Default Upper Warning Threshold for a specific sensor type:
config:#
defaultThresholds <sensor type> upperWarning <value>
Set the Default Lower Critical Threshold for a specific sensor type:
config:#
defaultThresholds <sensor type> lowerCritical <value>
Set the Default Lower Warning Threshold for a specific sensor type:
config:#
defaultThresholds <sensor type> lowerWarning <value>
Set the Default Deassertion Hysteresis for a specific sensor type:
config:#
defaultThresholds <sensor type> hysteresis <hy_value>
Set the Default Assertion Timeout for a specific sensor type:
config:#
defaultThresholds <sensor type> assertionTimeout <as_value>
Variables:
•
<sensor type> is one of the following numeric sensor types:
Sensor types
Description
absoluteHumidity
Absolute humidity sensors
relativeHumidity
Relative humidity sensors
temperature
Temperature sensors