LCD SETUP FUNCTIONS
Page 15
LCD Event Log
Five UPS Event Logs can be recorded.
1.
Press the “
ENTER
” button to activate the “
MAIN MENU
”.
2.
Press the “
▲
” and “
▼
” buttons to scroll to the “
Event Log
” option.
3.
Press the “
ENTER
” button to select the “
Event Log
” submenu.
4.
Press the “
▲
” and “
▼
” buttons to scroll through the “
Event Log
” submenu in the following table.
5.
Press the “
ESC
” button to return to UPS Status.
Event Log Submenu
Description
(X)
XXDXXHXXM (without Middle Atlantic Power Manager Software or
UPS-OLIPCARD)
- - / - - - -:- - (with Middle Atlantic Power Manager Software or UPS-OLIPCARD)
Event Content
LCD Settings Configuration
There are 22 UPS settings that can be configured by the user.
1.
Press the “
ENTER
” button to activate the “
MAIN MENU
”.
2.
Press the “
▲
” and “
▼
” buttons to scroll to the “
Configure
” option.
3.
Press the “
ENTER
” button to select the “
Configure
” submenu.
4.
Press the “
▲
” and “
▼
” buttons to scroll to the “
Configure
” submenu in the following table.
5.
Press the “
ENTER
” button to select the setting you want to configure.
The first configuration parameter will be displayed on the second column of LCD screen.
6.
Press the “
▲
” and “
▼
” buttons to scroll through the different parameters.
7.
Press the “
ENTER
” button to select the parameter you want to change.
You may be prompted to save the selection, if so press the “
ENTER
” button to save the setting. Some options are saved
and started automatically. (See the following table for more information.)
8.
Press the “
ESC
” button to cancel or return to the previous LCD menu.
Configuration
Submenu
Available Settings
Default
Setting
Description
Output Voltage
1
= [100V] [110V] [115V] [120V] [125V]
120V
Configures the output voltage.
Sync Freq Window
Range= [+/- 1%] [+/- 2%] [+/- 3%] [+/- 4%] [+/- 5%]
[+/- 6%] [+/- 7%] [+/- 8%] [+/- 9%] [+/-10%]
+/- 5%
Allows you to specify a permitted
output frequency range.
Bypass V Window
Range= [+10%/-10%] [+10%/-15%] [+10%/-20%]
[+15%/-10%] [+15%/-15%] [+15%/-20%]
+10%/-15
%
Allows you to specify a permitted
bypass output voltage range.
Bypass Condition
[Check Freq/Volt] [Check Volt Only] [No Bypass]
Check
Freq/Volt
Transfers UPS to Bypass mode
when the specified condition is
met.
ECO Mode
2
[Disable] [Enable]
Disable
When enabled, the UPS operates
in Bypass mode for higher
efficiency. In the event of a power
failure, the UPS transfers to the
inverter in less than 10 ms.
[V Range= +/-15%] [V Range= +/-10%] (for [Enable])
V Range=
+/-10%
Manual Bypass
[Disable] [Enable]
Disable
Enables or disables bypass mode
manually.