LCD SETUP FUNCTIONS
Page 16
Configuration
Submenu
Available Settings
Default
Setting
Description
UPS Diagnostic
[Battery Test] [Alarm Test] [Indicator Test] [Fan Test]
Battery
Test
Initiates a self-test for the
battery/alarm/indicator/fan.
[Activate?]
None
Audible Alarms
[Disable] [Enable]
Enable
Enables or disables audible
alarms.
EBM Number
= [0] [1] [2] [3] [4] [5] [6] [7] [8] [9] [10]
0
Used for setting the number of
extended battery modules in order
to calculate the correct estimated
runtime value.
Wiring Fault
[Disable] [Enable]
Disable
Enables or disables a check for the
input plug connection.
NCL Control
[Outlet On] [Outlet Off]
Outlet On
Controls the non-critical load
output via corresponding outlets.
Generator Mode
3
[Disable] [Enable]
Disable
Provides stable sine wave output
that is free of harmonics and
distortion without switching to
battery mode when running on
generator input power.
Communication
[Disable] [Enable]
Enable
Enables or disables all
communication.
Dry Relay Set
[I/P Power Fail] [Battery Low] [Summary Alarm]
[UPS On Bypass] [UPS Fail]
I/P Power
Fail
The dry relay may be set to close
when assigned to one of the five
available conditions.
Converter Mode
4
[Converter Off] [O/P Freq = 50Hz] [O/P Freq = 60Hz]
Converter
OFF
Sets the UPS converter to OFF,
50Hz, or 60Hz.
Screen Saver
[Disable] [1 Minutes] [5 Minutes]
5 minutes
When enabled, sets the LCD
screen saver to initiate after either
1 or 5 minutes of inactivity.
Clear Event Log
[Activate?]
None
Clears all LCD event log
information from the UPS.
Button OFF LOCK
[Disable] [Enable]
Disable
When enabled, disables ON/OFF
button functionality.
Charger Function
[SBM] [Constant]
SBM
When charging batteries, this sets
the charger function to either SBM
(smart battery management) or
constant voltage.
Signal Inputs
[Disable] [EPO] [ROO]
Disable
When enabled, sets the signal
inputs as either EPO (emergency
power off) or ROO (remote on or
off) to remote control the UPS. An
open circuit activates the EPO. In
ROO mode, an open circuit turns
the UPS off.
Charger Check
[Disable] [Enable]
Disable
When enabled, checks the electric
circuit of the charger.
Reset ReplaceBAT
[Activate?]
None
When the replace battery LED is
flashing, replace the battery and
reset the battery timer.
1
UPS-OL1500R/UPS-OL2200R/UPS-OL3000R, 100V is derated by 20%, 110V/115V is derated by 10%
Output voltage default setting varies by country.
2
This function can’t be set when Manual Bypass, Generator Mode or Converter Mode is enabled.
3
UPS has no bypass when Generator Mode is enabled.
4
UPS has no bypass when Converter Mode is enabled. This function can only be set before the UPS is on.