Aqua Tempo Power Series (with LAK) air cooled scroll chiller unit (50Hz) MCAC-ATSM-2013-11
106
250kW module
Load distribution
Unit: kg
No
Model
R1
R2
R3
R4
R5
R6
1
MGCSL-F30W/RN1
90
77
157
131
/
/
2
MGCSL-D30W/RN1
90
77
157
131
/
/
3
MGCL-F30W/RN1
81
68
139
112
/
/
4
MGCL-D30W/RN1
81
68
139
112
/
/
5
MGBL-F65W/RN1
170
180
145
155
/
/
6
MGBL-D65W/RN1
170
180
145
155
/
/
7
MGBL-F130W/RN1
350
340
295
285
/
/
8
MGBL-F200W/RN1
567
433
567
433
/
/
9
MGBL-F250W/RN1
373
344
487
462
539
395
12.4 Installation of damping devices
※
Damping devices must be provided between the unit and its foundation.
By means of the Φ15mm diameter installation holes on the steel frame of the unit base, the unit can be
fastened on the foundation through the spring damper. See
figure above
(Schematic diagram of installation
dimension of the unit) for details about center distance of the installation holes. The damper does not go with
the unit, and the user can select the damper according to the relevant requirements. When the unit is
350
Schematic diagram of installation dimension of the unit
1551
1551
18
88
Drainage
channel
Hole for anchor bolt
80
Concrete
Cement mortar
Drainage channel
25/30kW
55/60/65kW
130kW
200kW
250kW
Summary of Contents for Aqua Tempo Super Series
Page 48: ......
Page 62: ...MCAC ATSM 2013 11 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 61...
Page 69: ...Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz MCAC ATSM 2013 11 68...
Page 72: ...MCAC ATSM 2013 11 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 71...