MCAC-ATSM-2013-11 Aqua Tempo Power Series (with LAK) air cooled scroll chiller unit (50Hz)
121
8. The use
r’s attempt to repair the controller is prohibited, since improper repair may cause electric shock,
damages to the controller, and so on. If the user has any requirement of repair, please contact the
maintenance center.
12.3.2 Power supply specification
Items
Model
Outdoor power supply
Wiring
Power supply
Manual switch
Fuse
MGCSL-F30W/RN1
MGCSL-D30W/RN1
380~415V 3Ph
~
50Hz
50A
36A
10mm
2
(<30m)
MGCL-F30W/RN1
MGCL-D30W/RN1
380~415V 3Ph
~
50Hz
50A
36A
10mm
2
(<30m)
MGBL-F65W/RN1
380~400V 3Ph
~
50Hz
150A
100A
16mm
2
(<20m)
MGBL-D65W/RN1
380~415V 3Ph
~
50Hz
150A
100A
16mm
2
(<20m)
MGBL-F130W/RN1
380~400V 3Ph
~
50Hz
200A
150A
Base on the actual distance of the
wire, more than 35 mm
2
for each
module
MGBL-F200W/RN1
380~400V 3Ph
~
50Hz
400A
350A
According to the actual distance of
wiring,70mm2 or lager for each unit.
MGBL-F250W/RN1
380~400V 3Ph
~
50Hz
450A
300A
According to the actual distance of
wiring,150mm2 or lager for each unit.
12.3.3 Requirements of wiring connection
● No additional control components are required in the electric cabinet (such as relay, and so on), and the
power supply and control wires not connected with the electric cabinet are not allowed to go through the
electric box. Otherwise, electromagnetic interference may cause failure of the unit and control components
and even damages to them, which thus lead to protective failure.
● All cables led to the electrical box should be supported independently but by the electric box.
● The strong current wires generally pass the electrical box, and 220V alternating current may also pass the
control board, so wiring connection should conform to the principle of separation of strong current and weak
current, and the wires of power supply should be kept more than 100 mm away from the control wires.
● Only use 380-415V 3Ph 50Hz rated power supply for the unit, and the maximum allowable range of
voltage is 342V-418V.
● All electric wires must conform to local wiring connection norm. The suitable cables should be connected
to power supply terminal through wiring connection holes at the bottom of the electric cabinet. According to
Chinese standard, the user is responsible for providing voltage and current protection for the input power
supply of the unit.
● All power supplies connected to the unit must pass one manual switch, to ensure that the voltages on all
nodes of electric circuit of the unit are released when the switch is cut off.
● The cables of correct specification must be used to supply power for the unit. The unit should use
independent power supply, and the unit is not allowed to use the same power supply together with other
electric devices, to avoid over-load danger. The fuse or manual switch of the power supply should be
compatible with working voltage and current of the unit. In case of parallel connection of multiple modules,
the requirements of wiring connection mode and configuration parameters for the unit are shown in the
following figure.
● Some connection ports in the electric box are switch signals, for which the user needs to provide power,
and the rate voltage of the power should be 220-230V AC. The user must be aware that all power supplies
they provided should be obtained through power circuit breakers (provided by the user), to ensure that all
voltages on the nodes of the provided power supply circuit are released when the circuit breakers are cut off.
● All inductive components provided by the user (such as coils of contactor, relay, and so on) must be
suppressed with standard resistance-capacitance suppressors, to avoid electromagnetic interference, thus
leading to failure of the unit and its controller and even damages to them.