Aqua Tempo Power Series (with LAK) air cooled scroll chiller unit (50Hz) MCAC-ATSM-2013-11
12
Signal wire
mm
2
0.75×3-core with shielding
0.75×3-core with shielding
Control type
Wired controller
Wired controller
Safety protection device
1) Protection for over-high discharge pressure.
2) Protection for over-low suction pressure.
3) Power supply phase sequence protection.
4) Anti-freezing protection in cooling mode.
5) Anti-freezing protection in Winter.
6) Protection for compressor over current.
7) Protection for compressor overload.
8) Outlet and inlet water temperature difference protection.
9) Compressor discharge temperature protection.
10) Water flow cut-off protection.
11) Sensor malfunction protection.
12) Low ambient temperature drive-up protection
13) Low-temperature protection of shell and tube heat
exchanger.
Noise level
dB(A)
67
Operation water temp
℃
Cooling
:
0
~
17
(
Less than 5
℃
must add antifreeze
)
Heating
:
22
~
50
Ambient temp
℃
Cooling
:
-10
~
46 Heating
:
-10
~
21
Note:
Please refer to the water flow in the above table strictly to design and install.
All the above data is measured base on the following working condition:
1. Cooling mode: water side fouling factor: 0.086m
2
·℃
/kW, chilled water inlet/outlet: 12
℃
/ 7
℃
, and outdoor ambient temp.
35
℃
DB.
2. Heating mode: water side fouling factor: 0.086m
2
·℃
/kW, warm water inlet/outlet: 40
℃
/ 45
℃
, and outdoor ambient temp. 7
℃
DB/6
℃
WB.