Aqua Tempo Power Series (with LAK) air cooled scroll chiller unit (50Hz) MCAC-ATSM-2013-11
138
MGBL-F65W/RN1 outlook view
MGBL-F65W/RN1 module components description
No. Detail information
1
Detection of current of the compressor A1 (Protection code P4).
2
Detection of current of the compressor B1 (Protection code P5).
Current is not detected within the initial 5 seconds after the compressor is started up. When the current of the compressor is
detected to exceed protective value set (33A for constant speed compressor), it will be shut down and re-started after 3 min.
3
Power port for the current board.
4
T4: outdoor ambient temperature sensor (Fault code E7).
T3B: pipe temperature sensor of the condenser B (Fault code E6 and protection code P7).
T3A: pipe temperature sensor of the condenser A (Fault code E5 and protection code P6).
1) T4: if there is one system that requires starting outdoor fans, the fans are started through electric control of the unit. Start
outdoor fan A only, start A and B gears, and control the unit through T4.
2) T3B and T3A: when the electric control of the unit detects the temperature of the outdoor pipe T3A or T3B of the system
exceeds the protective temperature 65
℃
, the corresponding system will be shut down. And it will be re-started up, after the
temperature drops below the recovery temperature 60
℃
. Another system will be not affected.
3) T4, T3B and T3A: when the temperature sensor is detected to suffer open circuit or short circuit, fault alarm will occur.
●
When the main unit suffer fault of temperature sensor: the main unit and subordinate units will be shut down.
●
When the subordinate unit suffer fault of temperature sensor: the unit will be shut down, but other subordinate units will
not be affected.
5
Shell and tube low-temperature ant-freezing sensor (Fault code Eb).
6
Unit outlet water temperature sensor (Fault code E4).
Under refrigeration mode and heating mode, conduct adjustment according to the magnitude of unit outlet water
33
32
31
28
29
30
21
22
23
24 25 26
27
11
15
12
18
13
14
17
16
19
20
10 9 8 7 6 5
4
3
2
1
Summary of Contents for Aqua Tempo Super Series
Page 48: ......
Page 62: ...MCAC ATSM 2013 11 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 61...
Page 69: ...Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz MCAC ATSM 2013 11 68...
Page 72: ...MCAC ATSM 2013 11 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 71...