Aqua Tempo Power Series (with LAK) air cooled scroll chiller unit (50Hz) MCAC-ATSM-2013-11
6
13). Applicable temperature range
Mode
Ambient temperature range
Water outlet temperature range
Cooling
10
˚C ~46˚C
0~17
˚C(7˚C is default, less than 5˚C must add antifreeze)
-10
˚C ~46˚C
5
˚C ~17˚C(7˚C is default)
Heating
-10
˚C ~21˚C
22
˚C ~50˚C(45˚C is default)
Chilled outlet water temperature can be adjusted by wired controller
according to customer’s demand.
-15
˚C
Ambient temp. range
-10
˚C -5 ˚C 0 ˚C
5
˚C 10 ˚C 15 ˚C 20 ˚C 25 ˚C 30˚C 35 ˚C 40 ˚C 45 ˚C
Heating range
-10
˚C
21
˚C
Water outlet temp. range
5
˚C
50
˚C
17
˚C
45
˚C
22
˚C
0
˚C
Cooling range
0
˚C
17
˚C
Heating range
22
˚C
50
˚C
Cooling range
-10
˚C
46
˚C
50
˚C