2) Current protection
3) High temperature protection of condenser
High temperature protection of
condenser.
Yes
Clean heat exchanger.
Check the fan motor,
capacitor (1 phase) or
start up water pump.
Empty, vacuuming and
append
refrigerant
if
necessary.
Check power supply,
start up the unit after
normal power supply.
Replace PCB.
Inform the customer service
center.
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
Abnormal power supply.
Air is in system, filled too much
refrigerant(Generally
happened after maintenance.)
PCB mistakes to alarm.
Yes
Yes
The fin of heat exchanger is
dirty or aged in cooling mode.
Clean heat exchanger.
Replace PCB.
Replace
temperature
sensor.
Check the fan motor,
capacitor (1 phase).
Replace
installation
position of unit.
PCB mistakes to alarm.
No
The installation position of unit
results in bad heat transfer of
condenser.
Yes
Yes
Yes
Yes
No
In cooling mode, the fan motor
stop running, reversal and run
slowly.
The temperature sensor of
condenser bring drifting when
collect temperature.
No
No
No
Inform the customer service
center.
Current protection
The fin of heat exchanger is
dirty or aged in cooling mode,
or the shell and tube scaled
strong.
The
fan
motor
stopped
running in cooling mode,
reversal and run slowly. The
water pump didn
’t start up or
less water flow in heating.