MCAC-ATSM-2013-11 Aqua Tempo Power Series (with LAK) air cooled scroll chiller unit (50Hz)
95
10) Total outlet water temperature sensor malfunction
11) The unit outlet water temp. sensor malfunction
Total outlet water temperature
sensor malfunction
The unit outlet water temperature
sensor malfunction
The circuit of total outlet water
temperature sensor is broken.
Inform the customer service
center.
PCB mistakes to alarm.
The circuit of total outlet water
temperature sensor is shorten.
Replace PCB.
Fixed joint.
Replace
temperature
sensor.
Replace
temperature
sensor.
The joint of total outlet water
temperature sensor is loose.
Inform the customer service
center.
PCB mistakes to alarm.
The unit
’s circuit of outlet water
temperature sensor is broken.
Replace PCB.
Replace temperature sensor.
The unit
’s circuit of outlet water
temperature sensor is shorten.
Replace
temperature
sensor.
The unit
’s joint of outlet water
temperature sensor is loose.
Fixed joint.
Yes
No
No
No
No
Yes
Yes
Yes
Yes
No
No
No
No
Yes
Yes
Yes
Yes
Yes