Aqua Tempo Power Series (with LAK) air cooled scroll chiller unit (50Hz) MCAC-ATSM-2013-11
48
9 Capacity Tables
9.1
30kW module
Cooling:
Chilled water
outlet temp.
Ambient temp.(
℃
)
21.00
25.00
30.00
35.00
40.00
46.00
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
(
℃
)
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
5.00
33.59
8.81
31.63
9.08
29.84
9.36
28.20
9.65
26.42
10.13
24.31
10.64
6.00
34.72
8.94
32.66
9.22
30.79
9.51
29.07
9.80
27.27
10.29
25.11
10.80
7.00
35.93
9.13
33.77
9.41
31.80
9.70
30.00
10.00
28.17
10.50
25.97
11.03
8.00
37.04
9.40
34.78
9.69
32.72
9.99
30.84
10.30
28.99
10.82
26.76
11.36
9.00
38.09
9.49
35.73
9.79
33.58
10.09
31.62
10.40
29.75
10.92
27.49
11.47
10.00
39.53
9.63
37.05
9.93
34.79
10.24
32.73
10.56
30.83
11.08
28.52
11.64
11.00
40.63
9.73
38.05
10.03
35.69
10.34
33.54
10.66
31.63
11.19
29.29
11.75
12.00
41.56
9.87
38.88
10.18
36.44
10.49
34.22
10.82
32.30
11.36
29.94
11.92
13.00
42.31
9.95
39.54
10.26
37.02
10.58
34.73
10.90
32.82
11.45
30.46
12.02
14.00
43.36
10.02
40.48
10.33
37.87
10.65
35.49
10.98
33.58
11.53
31.19
12.10
15.00
43.92
10.07
40.97
10.38
38.29
10.70
35.85
11.03
33.95
11.58
31.57
12.16
Note:
The inlet/outlet water temperature difference is 5
℃
.