background image

4                                                                 

Specifications subject to change without notice.                                                                         IM-DHMSHA-02

SYSTEM REQUIREMENTS

Allow sufficient space for airflow and unit service. See Fig. 8 — on page 9 for the minimum required distances between the unit and walls or

ceilings.

Piping
IMPORTANT: Both refrigerant lines must be insulated separately.

• Table 3 lists the pipe sizes for the indoor unit. Refer to the outdoor unit’s installation instructions for other allowed piping lengths and

refrigerant information.

Table 3 — Indoor Unit Pipe Sizes 

WIRING

All wires must be sized per NEC (National Electrical Code) or CEC 

(Canadian Electrical Code) and local codes. See the rating plate and/

or the installation instructions of the compatible outdoor unit for MCA 

(minimum circuit amps) and MOCP (maximum over current 

protection) to correctly size the wires and the disconnect fuse or 

breakers respectively.

Recommended Connection Method for Power and 

Communication Wiring:

The main power is supplied to the outdoor unit. The field supplied 14/

3 power/communication wiring from the outdoor unit to the indoor 

unit consists of four (4) wires and provides the power for the indoor 

unit. Two wires are high voltage AC power, one is communication 

wiring and the other is a ground wire. Wiring between the indoor and 

outdoor unit is polarity sensitive. The use of BX wire is NOT 

recommended.
If installed in a high Electromagnetic field (EMF) area and

communication issues exists, a 14/2 stranded shielded wire can be

used to replace L2/N and (S) between outdoor unit and indoor unit

landing the shield onto ground in the outdoor unit only.

NOTE: The  main  power  is  supplied  to  the  outdoor  unit.

When disconnecting the power of the outdoor unit,

the  indoor  unit  would  lose  power.  A  disconnect

switch is not required on the Indoor unit side on

the wiring between the Outdoor and Indoor unit. A

3 pole disconnect may be used for extra protection

between the Indoor and Outdoor Unit. 

UNIT SIZES

12K

(115V)

9K

(208/230V)

12K

(208/230V)

18K

(208/230V)

24K

(208/230V)

30K

(208/230V)

36K

(208/230V)

GAS PIPE

in

1/2

3/8

1/2

1/2

5/8

5/8

5/8

(mm)

12.7

9.52

12.7

12.7

16

16

16

LIQUID PIPE

in

1/4

1/4

1/4

1/4

3/8

3/8

3/8

(mm)

6.35

6.35

6.35

6.35

9.52

9.52

9.52

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage

or improper operation.
Wires should be sized based on NEC and local codes.

WARNING

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage

or improper operation.

Be sure to comply with local codes while running wire from

the indoor unit to the outdoor unit.

Every wire must be connected firmly. Loose wiring may 

cause the terminal to overheat or result in unit malfunction. A 

fire hazard may also exist. Ensure all wiring is tightly 

connected.

No wire should touch the refrigerant tubing, compressor or 

any moving parts.

Disconnecting means must be provided and shall be located

within sight and readily accessible from the air conditioner.

Connecting cable with conduit shall be routed through the 

hole in the conduit panel.

CAUTION

Summary of Contents for DHMSHA Series

Page 1: ...l models may differ slightly TABLE OF CONTENTS SAFETY CONSIDERATIONS 2 PARTS LIST 3 SYSTEM REQUIREMENTS 4 WIRING 4 DIMENSIONS 5 CLEARANCES 9 INSTALLATION TIPS 10 INDOOR UNIT INSTALLATION 10 ELECTRICAL...

Page 2: ...NGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsaf...

Page 3: ...Part No Part Name Qty 1 Indoor Unit 1 2 Mounting Plate 1 3 Mounting Screw A ST3 9x25 C H 5 4 Anchor 5 5 Air Filter 1 6 Wireless Remote Control 1 7 Wireless Remote Control Holder 1 8 Wireless Remote C...

Page 4: ...es exists a 14 2 stranded shielded wire can be used to replace L2 N and S between outdoor unit and indoor unit landing the shield onto ground in the outdoor unit only NOTE The main power is supplied t...

Page 5: ...08 230V 208 230V 208 230V 208 230V 208 230V Height In mm 11 07 281 11 07 281 11 07 281 12 40 315 13 39 343 13 39 343 13 39 343 Width In mm 33 17 842 33 17 842 33 17 842 38 98 990 46 69 1186 46 69 1186...

Page 6: ...17 360 33 17 842 33 16 842 32 24 819 2 2 56 1 78 45 11 03 280 9 25 235 8 49 216 7 96 202 9 46 240 9 46 240 9 25 235 9 25 235 8 1 206 7 05 179 5 87 149 8 1 206 6 88 175 5 36 136 1 86 47 7 96 202 8 49...

Page 7: ...6 21 158 5 08 129 4 13 105 3 23 82 1 08 27 11 32 287 10 39 264 9 57 243 8 78 223 7 53 191 5 98 152 5 08 129 4 13 105 3 15 80 1 08 27 10 66 271 12 40 315 2 56 65 1 74 44 5 03 128 13 52 343 38 98 990 20...

Page 8: ...24 57 21 63 549 47 01 1194 20 91 531 2 24 57 2 25 57 2 24 57 13 51 343 2 25 57 12 10 307 14 98 380 14 26 362 12 54 319 11 05 281 9 71 247 4 53 115 4 34 110 4 33 110 4 53 115 9 70 246 12 53 318 14 25 3...

Page 9: ...es NOTE The top clearance recommended for proper return airflow is 5 9in 15cm Reduction of this clearance may decrease unit performance This may be reduced to 3 2in 80mm as long as the right and left...

Page 10: ...ides Attach the Mounting Plate to the Wall 1 Carefully remove the mounting plate which is attached on the back of the indoor unit 2 Using the stencil determine the wall hole position The mounting plat...

Page 11: ...iring on Indoor Unit High Wall Unit Size Indoor Fan Max Fuse CB Amp V PH HZ FLA HP Refer to outdoor unit installation instructions Indoor unit powered by the outdoor unit 12K 208 230 1 60 0 33 0 053 9...

Page 12: ...ring cover and close the indoor unit s front cover 10 Piping a Cut the pipe with a pipe cutter at 90 degrees see Fig 16 b Remove the service connection if provided with the unit Fig 16 Pipe Cutting c...

Page 13: ...cket if installed on the wall 1 Use the two screws supplied with the wireless remote control to attach the mounting bracket to the wall in a location selected by the customer and within operating rang...

Page 14: ...is a combination of flashing LEDs on the display panel or the front of the unit Some indoor units display error codes specifying failure modes in the outdoor units If possible always check the diagno...

Reviews: