1.2 Abbreviation
Unit element abbreviations
Abbreviation
Element
T1
Indoor room temperature
T2
Coil temperature of evaporator
T3
Coil temperature of condenser
1.3 Safety Features
Compressor three-minute delay at restart
Compressor functions are delayed for up to one minute
upon the first startup of the unit, and are delayed for up
to three minutes upon subsequent unit restarts.
Zero crossing detection error protection
If AC can not detect zero crossing signal for 4 minutes or
the zero crossing signal time interval is not correct, the unit
will stop and the LED will display the failure. The correct
zero crossing signal time interval should be between
6-13ms.
Automatic shutoff based on fan speed
If the indoor fan speed registers below 300RPM for 50s,
the unit ceases operation and the corresponding error
code is displayed on the indoor unit.
Current protection
The current exceeds setting value for certain time, the
compressor and outdoor fan will shut off.
Indoor fan delayed operation
• When the unit starts, the louver is automatically
activated and the indoor fan will operate after a period
of 4 seconds.
• If the unit is in heating mode, the indoor fan is
regulated by the anti-cold wind function.
Sensor redundancy and automatic shutoff
If one temperature sensor malfunctions, the air conditioner
ceases operation.
Refrigerant leakage detection
This function is active only when cooling mode is selected.
It will detect if the compressor is being damaged by
refrigerant leakage or by compressor overload. This is
measured using the coil temperature of evaporator T2
when the compressor is in operation.
1.4 Fan Mode
When fan mode is activated:
• The outdoor fan and compressor are stopped.
• Temperature control is disabled and no temperature
setting is displayed.
• The indoor fan speed can be set to high, medium, low,
or auto.
• The louver operations are identical to those in cooling
mode.
• Auto fan: In fan-only mode, AC operates the same as
auto fan in cooling mode with the temperature set at
24°C.
1.5 Cooling Mode
1.5.1 Compressor Control
When indoor room temperature T1 is lower than setting
value, the compressor and outdoor fan will shut off.
1.5.2 Indoor Fan Control
In cooling mode, the indoor fan operates continuously. The
fan speed can be set to high, medium, low, or auto.
1.5.3 Outdoor Fan Control
For on-off models, outdoor units just have one single fan
speed. The operation of outdoor fan is consistent with the
operation of compressor, except the following situations.
• High temperature protection of condenser
• Current protection
1.5.4 Evaporator Temperature Protection
When evaporator temperature drops below a configured
value, the compressor and outdoor fan ceases operations.
1.5.5 Condenser Temperature Protection
(for
some models)
When condenser temperature is more than setting value,
the compressor will stop.
1.6 Heating Mode(for heat pump models)
1.6.1 Compressor Control
When indoor room temperature T1 is higher than setting
value the compressor and outdoor fan will shut off.
1.6.2 Indoor Fan Control
• When the compressor is on, the indoor fan can be
set to high/med/low/auto. And the anti-cold wind
function has the priority.
• The indoor fan speed will adjust according to the value
of T1-TS.
Summary of Contents for Forest MOAA31-12CN1-NB8
Page 1: ...FOREST R410A ONOFF CONTROL TM_AF_R410A_ONOFF_SA_NA_2008 TECHNICAL MANUAL ...
Page 8: ...Specifications Page 8 3 2 Outdoor Unit 12k ...
Page 9: ...Specifications Page 9 18k ...
Page 10: ...Specifications Page 10 24k ...
Page 12: ...Specifications Page 12 24k ...
Page 14: ...Specifications Page 14 18k 24k ...