background image

10

ELECTRICAL  WORK

Minimum norminal cross-sectional 
area of conductors: 

Rated current 
of appliance
         (A)

>3  and  <6

>6  and  <10

>10  and  <16
>16  and  <25

Nominal cross-sectional 
                 area

2

                (mm )

0.75

1

1.5

2.5

NOTE

: The cable size and the current of the fuse 

or switch are determined by the maximum current
indicated on the nameplate which located on the 
side panel of the unit. Please refer to the nameplate 
before selecting the cable, fuse and switch.
  

Connect the cable to the outdoor unit

Connect the cable to the indoor unit

NOTE: Before performing any electrical 
work, turn off the main power to the system.

,

1. The inside and outside connecting cable can 
    be connected without removing the front grille.
2. The indoor power cord type is H05VV-F or
    H05V2V2-F, the outdoor power cord and 
    interconnected cord type is H07RN-F.
3. Lift the indoor unit panel up, remove the 
    electrical box cover by loosening the screw
    as shown in Fig.22.
4. Ensure the colour of wires of outdoor unit 
    and the terminal Nos. are the same to the 
    indoor s respectively.
5. Wrap those cables not connected with 
    terminals with insulation tapes, so that they 
    will not touch any electrical components. 
    Secure the cable onto the control board with 
    the cord clamp.

,

Terminal block of indoor unit

Fig.22

To outdoor unit

To outdoor unit

1. Remove the cover control from the unit by 

loosening the 3 screws. See Fig.23.

2. Dismount caps on the conduit panel.
3. Temporarily mount the conduit tubes(not included) 
    on the conduit panel.
4. Properly connect both the power supply and low 
    voltage lines to the corresponding terminals on
    the terminal block.
5. Ground the unit in accordance with local codes.
6. Be sure to size each wire allowing several inches 
    longer than the required length for  wiring.
7. Use lock nuts to secure the conduit tubes.  

G

Cover control

Over 1 3/5in.(40mm)

Terminal block

Conduit panel

Connecting 
cable

Power supply 
cord

Outdoor unit

Fig.23a

L    N    S

L1  L2    S

or

Electrical box
cover

Front Panel

Summary of Contents for INVERTER SPLIT TYPE ROOM AIR CONDITIONER

Page 1: ...ompletely before installing the product If the power cord is damaged replacement work shall be performed by authorised personnel only Installation work must be performed in accordance with the nationa...

Page 2: ...use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the...

Page 3: ...ring standard regulation and this installation instructions An independent circuit and single outlet must be used If electrical circuit capacity is not enough or defect found in electrical work it wil...

Page 4: ...ated by arrows from wall or other obstacles Do not place animals and plants in the path of the air inlet or outlet Take the air conditioner weight into account and select a place where noise vibration...

Page 5: ...e 60c m abo ve 30cm above Air Filter Air Outlet 30cm above Wrapping tape B 200cm above Additional drain pipe Accessories Parts you must purchase Consult the dealer about the pipe size 6 35 9 53 12 7 9...

Page 6: ...mensions are in mm unless otherwise stated 1 Determine hole positions according to the diagramdetailed in Fig 5 Drill one 1 hole 65mm slanting slightly to outdoor side 2 Always use wall hole conduit w...

Page 7: ...the indoor unit with a cushioning material between the indoor unit and the wall Get it out after finish piping 4 Push the lower part of the indoor unit up on the wall then move the indoor unit from s...

Page 8: ...se sloped downward to drain out the condensed water smoothly CAUTION Install the outdoor unit on a rigid base to prevent increasing noise level and vibration Determine the air outlet direction where t...

Page 9: ...r tube pipe in a downward direction as you remove burrs in order to avoid dropping burrs into the tubing Pipe Reamer Point down Fig 16 Fig 17 Outdoor unit dimension mm WxHxD A mm B mm 530 290 484 600...

Page 10: ...air conditioner and explain to the client until the problem is solved 2 Power voltage should be in the range of 90 110 of rated voltage 3 The creepage protector and main power switch with a 1 5 times...

Page 11: ...oosening the screw as shown in Fig 22 4 Ensure the colour of wires of outdoor unit and the terminal Nos are the same to the indoor s respectively 5 Wrap those cables not connected with terminals with...

Page 12: ...connecting means must be provided and shall be located within sight from and readily accessible from the air conditioner Connecting cable with conduit shall go through the hole of the conduit panel No...

Page 13: ...the fixed wiring and have an air gap contact separation of at least 3mm in each active phase conductors CAUTION CAUTION CAUTION CAUTION Air and moisture in the refrigerant system have undesirable eff...

Page 14: ...ully open the handle Lo of the manifold valve 4 Operate the vacuum pump to evacuate After starting evacuation slightly loose theflare nut of the Lo valve on the gas pipe side and check that the air is...

Page 15: ...If bubbles come out the pipes have leakage 2 Leak detector Use the leak detector to check for leakage Test running Safety and leakage check 14 TEST RUNNING Manual control button AUTO COOL Perform tes...

Page 16: ...CS120I BP9A1 LH 202000192327 20110613 The design and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details...

Reviews: