Meanwhile the maximum running frequency will
be adjusted according to the outdoor ambient
temp.
43
41
38
T4LimFre1_ADD
No limit
T4LimFre2_ADD
T4LimFre3_ADD
42
39
37
49
46
T4LimFre4_ADD
T4LimFre5_ADD
48
45
Heating mode
T1 Ts
4
0
a
3
1
-1
3
1
2
0
b
c
d
e
f
2
Capacity area
a
b
c
d
e
f
Norm code (N)
3
2
1.5
1
0.5
0
Model
9K
12K
18K
HP
1.0
1.2
1.5
Plus all the indoor capacity request together,
then modify it by T4
When there’s only one indoor unit
Heating
Outdoor temperature (T4)
<
0
℃
<
12
℃
12
℃
~ 17
℃
≥17
℃
Modify rate
120%
80%
40%
20%
When there’re more than one indoor unit
Heating
Outdoor temperature (T4)
<
0
℃
<
12
℃
12
℃
~ 17
℃
≥17
℃
Modify rate
120%
100%
80%
60%
Note: The final result is integer.
Then modify it according to T2
average(correction):
Note:Average value of T2
:
Sum T2 value of all
indoor units)/(indoor units number
According to the final capacity request to
confirm the operating frequency, as following
table.
Frequency
(Hz)
0
HEAT
_F1
HEAT
_F2
…
HEAT
_F15
HEAT
_F16
Amendatory
capacity
demand.
0
1
2
…
15
16
Heating capacity improved in low ambient
heating
In heating mode, when
T2<T2_ExitT4LowFre_ADD , and T4<-4
℃
,
there’s frequency elevation:
elevated frequency= Recent frequency * 110%
When T2> T2_ExitT4LowFre_ADD-2 and T4>-6,
the highest frequency can’t exceed F17
When T2> T2_ExitT4LowFre_ADD-4 and T4>-8,
the highest frequency can’t exceed F18
When T2> T2_ExitT4LowFre_ADD-6 and T4>-10,
the highest frequency can’t exceed F19
Summary of Contents for M2OC-18HFN1-M
Page 19: ...8 Wiring Diagrams 8 1 Wiring diagram of 1 drive 2 outdoor M2OC 18HFN1 M M2OD 18HFN1 M...
Page 20: ...PCB board of M2OC 18HFN1 M M2OD 18HFN1 M...
Page 21: ...IPM board of M2OC 18HFN1 M...
Page 22: ...IPM board of M2OD 18HFN1 M...
Page 23: ...8 2 Wiring diagram of 1 drive 3 outdoor M3OD 27HRDN1 M M3OC 30HRFN1 M...
Page 24: ...PCB board of M3OC 30HRFN1 M...
Page 25: ...IPM board of M3OC 30HRFN1 M...
Page 26: ...PCB board of M3OD 27HRDN1 M...
Page 27: ...IPM board of M3OD 27HRDN1 M...
Page 28: ...8 3 Wiring diagram of 1 drive 4 outdoor M4OC 36HRFN1 M...
Page 29: ...PCB board of M4OC 36HRFN1 M...
Page 30: ...IPM board of M4OC 36HRFN1 M...
Page 31: ...PFC board of M4OC 36HRFN1 M...
Page 66: ...IPM for dual tri zone IPM for qua zone P N for dual tri zone...
Page 67: ...P N for qua zone...
Page 68: ...bridge rectifier for dual tri zone bridge rectifier for qua zone...
Page 69: ...Remark Measure the DC voltage between and port The normal value should be 190V 250V...
Page 71: ...Two ports of the inductance Inductance...
Page 72: ......
Page 77: ......
Page 79: ......
Page 81: ......
Page 83: ......
Page 96: ...6 EXV check Disconnect the connectors...
Page 98: ...Red Blue Red Yellow...
Page 99: ...Brown Orange Brown White...
Page 114: ...Screws of front panel Screws of right rear panel Screws of top cover...
Page 128: ......