1.If the compressor frequency keeps lower than
RET_OIL_FREQ1_ADD for
RET_OIL_TIME1_ADD,the AC will rise the
frequency to RET_OIL_FREQ2_ADD for
RET_OIL_TIME2_ADD and then resume to
former frequency.
2.During the oil return process, the EXV will keep
300p while the indoor units will keep the current
running mode.
7.3.11 Compressor preheating functions
----Preheating permitting condition:
If T4(outdoor ambient temperature)
<
3
℃
and
newly powered on or if T4
<
3
℃
and compressor
has stopped for over 3 hours, the compressor
heating cable will work.
----Preheating mode:
A weak current flow through the coil of
compressor from the wiring terminal of
compressor, then the compressor is heated
without operation.
----Preheating release condition:
If T4
>
5
℃
or the capacity demand isn
’t zero,
preheating function will stop.
7.3.12 Compressor crankcase heater
----Preheating permitting condition:
①
When T4<3
℃
within 5 seconds of being
plugged in, the crankcase heater will be
active.
②
When T4<3
℃
and the compressor is not
running for 3 hours, the crankcase heater will
be active.
----Preheating release condition:
When T4
≧
5
℃
or the indoor has capacity
demand, the crankcase heater will stop work.
7.4 Control and Functions
7.4.1 Capacity Request Calculation
Total capacity Request=
Σ(Norm code × HP) /10×
modify rate+ correction
Cooling mode:
T1 Ts
3
1
1
e
c
a
4
2
0
2
3
0
1
f
d
b
Capacity area
a
b
c
d
e
f
Norm code (N)
3
2 1.5 1 0.5 0
Model
9K
12K
18K
HP
1.0
1.2
1.5
Note: The final result is integer.
Plus all the indoor capacity request together, then
modify it by T4
When
there’s only one indoor unit
Cooling
Outdoor temperature (T4)
>
29
℃
18
℃
~ 29
℃
<17
℃
Modify rate
100%
60%
40%
When there’re more than one indoor unit
Cooling
Outdoor temperature (T4)
>
25
℃
17
℃
~ 25
℃
<17
℃
Modify rate
100%
80%
40%
Note: The final result is integer.
In low ambient cooling mode, modify rate is fixed
as 40%.
According to the final capacity request to
confirm the operating frequency, as following
table.
Frequency
(Hz)
0
COO
L_F1
COO
L_F2
…
…
COOL
_F15
COO
L_F1
6
Amendatory
capacity
demand.
0
1
2
…
…
15
16
Summary of Contents for M2OC-18HFN1-M
Page 19: ...8 Wiring Diagrams 8 1 Wiring diagram of 1 drive 2 outdoor M2OC 18HFN1 M M2OD 18HFN1 M...
Page 20: ...PCB board of M2OC 18HFN1 M M2OD 18HFN1 M...
Page 21: ...IPM board of M2OC 18HFN1 M...
Page 22: ...IPM board of M2OD 18HFN1 M...
Page 23: ...8 2 Wiring diagram of 1 drive 3 outdoor M3OD 27HRDN1 M M3OC 30HRFN1 M...
Page 24: ...PCB board of M3OC 30HRFN1 M...
Page 25: ...IPM board of M3OC 30HRFN1 M...
Page 26: ...PCB board of M3OD 27HRDN1 M...
Page 27: ...IPM board of M3OD 27HRDN1 M...
Page 28: ...8 3 Wiring diagram of 1 drive 4 outdoor M4OC 36HRFN1 M...
Page 29: ...PCB board of M4OC 36HRFN1 M...
Page 30: ...IPM board of M4OC 36HRFN1 M...
Page 31: ...PFC board of M4OC 36HRFN1 M...
Page 66: ...IPM for dual tri zone IPM for qua zone P N for dual tri zone...
Page 67: ...P N for qua zone...
Page 68: ...bridge rectifier for dual tri zone bridge rectifier for qua zone...
Page 69: ...Remark Measure the DC voltage between and port The normal value should be 190V 250V...
Page 71: ...Two ports of the inductance Inductance...
Page 72: ......
Page 77: ......
Page 79: ......
Page 81: ......
Page 83: ......
Page 96: ...6 EXV check Disconnect the connectors...
Page 98: ...Red Blue Red Yellow...
Page 99: ...Brown Orange Brown White...
Page 114: ...Screws of front panel Screws of right rear panel Screws of top cover...
Page 128: ......