51
8.4.9 Auto-Restart function
The indoor unit is equipped with auto-restart function, which is carried out through an auto-restart
module. In case of a sudden power failure, the module memorizes the setting conditions before the
power failure. The unit will resume the previous operation setting (not including Swing function)
automatically after 3 minutes when power returns.
If the memorization condition is forced cooling mode, the unit will run in cooling mode for 30 minutes
and turn to drying mode with 24
℃
settin
g temp.
If AC is off before power off and AC is required to start up now, the compressor will have 20 seconds
delay when power on. If AC is on before power off and AC is required to start up now, the compressor
will have 3 minutes delay when power on.