MCAC-PDSM-2013-04 Midea Precision AC Technical Manual-Down Delivery Series
31
Outdoor coil
(Single
outdoor unit)
No. of rows
\
3
Tube pitch(a)×row pitch(b)
mm
25.4×22
Fin spacing
mm
2.2
Fin type
\
Hydrophilic aluminum fin
Pipe outside dia. and type
mm
Ɏ
9.52
Inner grooved copper pipe
Coil (W×D)
mm
2,250×1,219.2
Number of circuits
\
18
Indoor air flow
m
3
/h 24,800
Indoor external static pressure
Pa
20
Indoor drain pipe I.D.
mm
Ɏ
30
Indoor noise level
dB(A)
İ
72
Outdoor noise level
dB(A)
İ
66
Refrigerant
Type \
R410A
Recharged (After installation)
g
17,000×2
Control
\
Thermostatic expansion valve
Maximum refrigeration pipe pressure
MPa
4.4
Refrigerant
pipe
Max. pipe length
m
60
Max. difference in level (O.U. up)
m
20
Max. difference in level (O.U.
down)
m 5
Connection
wire
Indoor power wire
mm
2
3×10.0mm
2
˄
A,B,C
˅
+2×6.0mm
2
˄
N,GND
˅
Outdoor power wire
mm
2
(4×1.0mm
2
)+ (4×1.0mm
2
)
Signal wire
mm
2
(4×1.0mm
2
)+ (4×1.0mm
2
)
Filter \
G4
Indoor unit
Net dimension (W×H×D)
mm
2,685×1,971×870
Net weight
kg
920
Outdoor unit
(Single)
Net dimension (W×H×D)
mm
2,480×1,290×690(No include supporting bar)
Net weight
kg
220
Notes:
1. The nominal cooling capacity is based on the following conditions. Indoor temperature: 24°CDB, 17°CWB;
Outdoor temperature: 35°CDB, pipe length is 10 meters.
2. The noise is measured in the semi suppression lab.
3. Specifications are subject to change without prior notice for product improvement.