Air-cooled modular chiller unit
53
9.2
MCC(D)H65A-SA3L
Cooling
Chilled water
outlet temp.
Ambient temp.(
℃
)
21.00
25.00
30.00
35.00
40.00
46.00
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
(
℃
)
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
5.00
72.77
17.97
68.52
18.52
64.64
19.10
61.10
19.69
57.25
20.67
52.67
21.70
6.00
75.23
18.25
70.77
18.81
66.70
19.39
62.99
19.99
59.08
20.99
54.41
22.04
7.00
77.85
18.62
73.17
19.19
68.90
19.79
65.00
20.40
61.04
21.42
56.27
22.49
8.00
80.26
19.18
75.36
19.77
70.90
20.38
66.82
21.01
62.81
22.06
57.97
23.17
9.00
82.52
19.36
77.41
19.96
72.76
20.58
68.51
21.22
64.47
22.28
59.57
23.39
10.00
85.65
19.65
80.27
20.26
75.38
20.89
70.91
21.53
66.80
22.61
61.79
23.74
11.00
88.04
19.85
82.44
20.46
77.33
21.09
72.68
21.75
68.54
22.83
63.47
23.98
12.00
90.06
20.14
84.24
20.76
78.95
21.40
74.13
22.06
69.98
23.17
64.87
24.33
13.00
91.66
20.30
85.67
20.93
80.21
21.57
75.25
22.24
71.11
23.35
65.99
24.52
14.00
93.94
20.44
87.72
21.07
82.05
21.72
76.90
22.40
72.75
23.52
67.58
24.69
15.00
95.15
20.54
88.76
21.18
82.95
21.83
77.67
22.51
73.55
23.63
68.41
24.81
Note:
The inlet/outlet water temperature difference is 5
℃
.
Summary of Contents for MCCDH30A-TA3SL
Page 37: ...Air cooled modular chiller unit 37 MCCH65A SA3L...
Page 38: ...Air cooled modular chiller unit 38 MCCD65A SA3L...
Page 40: ...Air cooled modular chiller unit 40 MCCH130A SA3L...
Page 41: ...Air cooled modular chiller unit 41 185 kW module...
Page 46: ...Air cooled modular chiller unit 46 130 kW module...
Page 48: ...Air cooled modular chiller unit 60 200kW module...
Page 78: ...Air cooled modular chiller unit 78 65kW module 130kW module...
Page 153: ...Air cooled modular chiller unit Fig 4 70 Fig 4 71...