Air-cooled modular chiller unit
57
9.4
MCCH185A-SA3
Cooling:
Chilled water outlet
temp.
Ambient temp.(
℃
)
21.00
25.00
30.00
35.00
40.00
46.00
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
(
℃
)
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
5.00
207.12
55.49
195.03
57.20
183.99
58.97
173.90
60.80
162.94
63.83
149.91
67.03
6.00
214.11
56.35
201.42
58.09
189.84
59.89
179.27
61.74
168.15
64.83
154.87
68.07
7.00
221.59
57.50
208.26
59.28
196.10
61.11
185.00
63.00
173.72
66.15
160.17
69.46
8.00
228.44
59.22
214.49
61.06
201.78
62.94
190.18
64.89
178.77
68.13
165.00
71.54
9.00
234.87
59.80
220.33
61.65
207.08
63.55
194.99
65.52
183.49
68.80
169.54
72.24
10.00
237.19
60.70
222.30
62.57
208.73
64.51
196.36
66.50
184.97
69.83
171.10
73.32
11.00
243.81
61.29
228.28
63.19
214.15
65.14
201.27
67.16
189.80
70.52
175.75
74.04
12.00
249.38
62.19
233.29
64.11
218.64
66.10
205.29
68.14
193.80
71.55
179.65
75.13
13.00
253.84
62.69
237.23
64.63
222.13
66.63
208.37
68.69
196.91
72.12
182.74
75.73
14.00
260.15
63.12
242.91
65.08
227.23
67.09
212.96
69.16
201.46
72.62
187.15
76.25
15.00
263.49
63.43
245.79
65.40
229.71
67.42
215.09
69.50
203.69
72.98
189.43
76.63
Note:
The inlet/outlet water temperature difference is 5
℃
.
Summary of Contents for MCCDH30A-TA3SL
Page 37: ...Air cooled modular chiller unit 37 MCCH65A SA3L...
Page 38: ...Air cooled modular chiller unit 38 MCCD65A SA3L...
Page 40: ...Air cooled modular chiller unit 40 MCCH130A SA3L...
Page 41: ...Air cooled modular chiller unit 41 185 kW module...
Page 46: ...Air cooled modular chiller unit 46 130 kW module...
Page 48: ...Air cooled modular chiller unit 60 200kW module...
Page 78: ...Air cooled modular chiller unit 78 65kW module 130kW module...
Page 153: ...Air cooled modular chiller unit Fig 4 70 Fig 4 71...