Air-cooled modular chiller unit
Electric control box
Total water outlet
temp sensor
Water intlet
Water outlet
Installation of multi-module water system pipeline
1)
Installation mode I (recommended installation mode)
n : the module quantity, max8
No.1 unit
No.0 address(main unit)
No.n unit (n≤8)
No.(n-1) unit
No.(2n-3) address
No.(2n-1) address
No.1 address
No.(2n-4) address
No.(2n-2) address
Pump
Drill dead hole at the
position, and move the
total effluent temperature
sensor at No.0 address to
the position
Water flow switch
Installation mode B: less than 8 modules
2)
Installation mode II
n : the module quantity, max8
Water flow switch
Drill dead hole at the
position, and move the
total effluent temperature
sensor at No.0 address to
the position
No.1 unit
No.0 address(main unit)
No.n unit (n≤8)
No.(n-1) unit
No.(2n-3) address
No.(2n-1) address
No.1 address
No.(2n-4) address
No.(2n-2) address
Pump
Installation mode B: less than 8 modules
1
.2.7 Installation of water system pipeline for 200kW module
Summary of Contents for MCCDH30A-TA3SL
Page 37: ...Air cooled modular chiller unit 37 MCCH65A SA3L...
Page 38: ...Air cooled modular chiller unit 38 MCCD65A SA3L...
Page 40: ...Air cooled modular chiller unit 40 MCCH130A SA3L...
Page 41: ...Air cooled modular chiller unit 41 185 kW module...
Page 46: ...Air cooled modular chiller unit 46 130 kW module...
Page 48: ...Air cooled modular chiller unit 60 200kW module...
Page 78: ...Air cooled modular chiller unit 78 65kW module 130kW module...
Page 153: ...Air cooled modular chiller unit Fig 4 70 Fig 4 71...